Rectify interference
6 720 643 196 (2010/02)
22
11.
Is a ceramic power resistor connected to
relay X52 on the inverter circuit board?
yes:
The resistor should have 16 ohm, replace if neces-
sary. Didn’t that help?
Æ
12
no:
The resistance must be 16 ohm.
B
Connect the resistor to X52.
Didn’t that help?
Æ
12
12.
Are the condensers connected to the
inverter circuit board?
IMPORTANT! The condensers may have
voltage left even if the machine is
switched off.
yes:
Are the condensers connected to TB-P2, TB-C1 and
TB-N1.
B
Compare the connection with the wiring diagram,
correct if necessary.
Didn’t that help?
Æ
13
no:
B
Connect the condensers on TB-P2, TB-C1 and TB-
N1.
Didn’t that help?
Æ
13
13.
Is (TB-N1)--(TB-P2) => 450-680VDC.
Is (TB-N1)--(TB-C1) => 225-340VDC.
Is (TB-C1)--(TB-P2) => 225-340VDC.
yes:
Æ
14
no:
Didn’t that help?
Æ
14
14.
B
Check the wiring between the inverter
circuit board and compressor.
Terminal block on inverter circuit board -
> Cable colour -> Terminal block on com-
pressor. TB-U -> black -> U TB-V -> brown
-> V TB-W -> grey -> W
yes:
Æ
15
no:
B
Replace wiring if burnt.
If the compressor does not run and the wiring is
incorrectly installed, the compressor is probably bro-
ken.
15.
Is the voltage between (TB-U)--(TB-V),
(TB-V)--(TB-W) and (TB-W)--(TB-U)?
yes:
Æ
16
no:
Inverter circuit board defective.
B
Replace inverter circuit board.
Didn’t that help?
Æ
16
16.
If a specific alarm code appears in the
rego window, see separate fault tracing
tree.
The heat pump does not run, troubleshooting the inverter section
Check
Action
Tab. 20