69
INDEX
Technical information
Technical information
The heat pump’s factory settings
The table shows the factory settings for all the settings that can
be changed by the installer.
Sensor table
The table shows all sensor resistance at
different temperatures.
Temperature (
ºC)
k
Ω
-40
154.300
-35
111.700
-30
81.700
-25
60.400
-20
45.100
-15
33.950
-10
25.800
-5
19.770
0
15.280
5
11.900
10
9.330
15
7.370
20
5.870
25
4.700
30
3.790
35
3.070
40
2.510
45
2.055
50
1.696
55
1.405
60
1.170
65
0.980
70
0.824
75
0.696
80
0.590
85
0.503
90
0.430
Menu Setting
Factor y setting
1.1
Temp. incr. / decr.
4
1.2
Temp. fi ne-tune
0º
1.3
Heat curve adjustment
0º
1.4
Heat curve hysteresis
5º
1.5
Mix. valve incr/decr
4
1.6
Mix. valve fi ne-tune
0º
1.7
Adapting the mixing valve curve
0º
1.8
Mix. valve curve neutral zone
3º
1.9
Mixing valve curve max at GT4
60º
1.10
Setting the room temperature
20º
1.11
Setting the room sensor infl uence
5
1.12
Setting of holiday function
0 days
1.13
Remote control temperature
not active
1.14
Setting of summer disconnection
18º
2.1
Number of hours for extra hot water
0 hours
2.2
hot water peak menu is used
not active
2.3
Setting of room hot water temperature.
51º
2.4
Setting of DHW hysteresis
4º
4.1
Clock setting HP accord. to clock
not active
4.1.1
Setting level heat pump +/-
0º
4.2
Clock setting additional heat according
to clock
not active
4.3
Clock setting hot water according
to clock
not active
5.2
Select conn capacity electr. cass.
2/3
5.4
Select the function only additional heat
off
5.5
Select function additional heat
yes
5.7
Selecting external controls
0
5.10
Selection of the operation alt. P2
P2 cont. operat
5.11
Selection of the operation alt. P3
P3 with comp.
8.1
Setting the additional heat timers
60 minutes
8.3.4
Ramp time open
20 min
8.3.5
Ramp time close
3 min