7. Check that the rotor’s inlet surfaces are not covered with dust or other
impurities. NB: Avoid touching the rotor inlet and outlet surfaces with your
hands or tools.
8. Check the pressure balance. To ensure correct function of the purging
sector, the negative pressure at P3 should be greater than the negative
pressure at P2 (min. diff. 25 Pa). Otherwise an ETET-TR trim damper can
be used on the extract air side in order to throttle in the correct pressure
balance.
Example:
Measurement outlets for P2: Downstream supply air fan (SF) generates
negative pressure in relation to the atmospheric pressure (atm), e.g. -100 Pa
Measurement outlets for P3: Downstream extract air fan (EF) and any trim
damper generate greater negative pressure than at P2, e.g. -125 Pa.
–
+
25 Pa
P3
P2
-100
Pa
-125
Pa
P1
P4
P
≈
1 atm
(101 kPa)
Trim damper
Measurement outlets for pressure balance – unit with control equipment (code MX).
–
+
–
+
25 Pa
P3
P2
-100
Pa
-125
Pa
P1
P4
P
≈
1 atm
(101 kPa)
Trim damper
Measurement outlets for pressure balance – unit without control equipment (code UC, MK, US).