Operation and Maintenance Instructions

Envicooler

2001-03-09

Air handling with the focus on LCC

5. Fault Tracing and Searching for Leakage

5.1 Fault-tracing Schedule 

SYMPTOM

POSSIBLE CAUSE

REMEDIAL MEASURE

Too high temperature in 
cooled component/medium

The power supply has been interrupted.

Check the control/safety switches and 
fuses.

No flow or poor flow across the 
evaporator.

Check that nothing is blocking the flow.
Check that the system is well purged of 
air.

The thermostat/control equipment is 
incorrectly set/faulty.

Adjust the setting or replace the 
equipment.

The compressor doesn’t work.

See under “Compressor”

The compressor doesn’t 
work.

The power supply has been interrupted.

Check the control/safety switches and 
fuses.

The safety circuit has switched out the 
compressor. Pressure switches, 
temperature monitor, flow monitor, anti-
frosting protection or motor protection.

Check and reset if required.

Faulty compressor.

Determine the fault. Replace the 
compressor.

The low-pressure switch 
switches out the 
compressor.

Too little refrigerant.

There is a leak in the system. Seal the 
leak and charge with refrigerant.

No flow or poor flow across the 
evaporator.

Check the flow.
Check the static pressure in the 
expansion vessel.
Check the circulation pump.

Too high glycol content.

Check the glycol content.

Faulty expansion valve.

Check, replace.

Faulty low-pressure switch.

Check, replace.

The high-pressure switch 
switches out the 
compressor.

No flow or poor flow across the 
condenser.

Check the flow across the condenser. 
Check the static pressure in the 
expansion vessel.
Check the circulation pump.

Too much refrigerant in the system.

Reduce the refrigerant volume.

Faulty high-pressure switch.

Check, replace.

Substantial frosting on the 
evaporator.

The expansion valve is incorrectly set/
faulty.

Check, replace.

Too little refrigerant.

Check in the sight glass. The system is 
leaking; seal the leakage; charge with 
refrigerant.

The evaporator is fouled.

Check the flow, filter if fitted, clean the 
evaporator if needed.

Summary of Contents for Envicooler

Page 1: ...Air handling with the focus on LCC Cooling Unit for Producing Chilled Water Envicooler Operation and Maintenance Instructions ...

Page 2: ... 350 43 VÄXJÖ Sweden Street address Sjöuddevägen 7 Phone 46 0 470 75 88 00 Telefax 46 0 470 75 88 77 Seller Service Post address Post address Telephone Telephone Other System Data Type of unit Order number Year manufactured Supply voltage Refrigerant SAQ approved HP Hydrostatic test ...

Page 3: ...____ 7 3 1 Regulations for Commissioning________________________________________ 7 3 2 Checklist ___________________________________________________________ 8 4 Maintenance Instructions and Procedures __________________________________ 9 4 1 General ____________________________________________________________ 9 4 2 Requirements by Authorities according to the Refrigerant Act ______________ 9 4 3 P...

Page 4: ...id to gas The cold suction gas that now has absorbed heat from the cooled space medium is sucked back into the compressor where it is compressed and heats up In all fully hermetic compressors the suction gas is also used to cool the electric mo tor that drives the compressor The refrigerant now contains heat from the component being chilled heat from the compressor motor and heat generated by comp...

Page 5: ...50 Hz Size Rec fuse Rec cable section EVC 1610 EVC 2410 EVC 3110 EVC 4020 EVC 4820 EVC 6220 EVC 7830 EVC 9330 20 AT 25 AT 35 AT 50 AT 50 AT 63 AT 80 AT 100 AT 4 mm2 6 mm2 10 mm2 16 mm2 16 mm2 25 mm2 35 mm2 50 mm2 Envicooler 251 252 External start signal Potential free NO 253 254 Group alarm Potential free NO C1 C2 C3 C4 SET AL prg oC XC440C Dixell 1 2 Set point To show the set point press the SET ...

Page 6: ...with these cooling units One piece cooling units charged with 3 kg or less refrigerant are treated in system cal culations as if they didn t contain any refrigerant at all This means that you can add or include any number of one piece cooling units of the type described above in a sys tem without being required to take increased refrigerant volume into consideration 2 2 One piece Units containing ...

Page 7: ...he system according to an accompanying checklist complete with commissioning record A copy of the Commis sioning Record shall first be signed by the technician who has commissioned the unit then be signed by the seller and after that be sent in to IV Produkt The validity of the product warrantee is conditional on the system having been correctly commissioned No modifications in the machine are per...

Page 8: ... you ve cancelled any interlock in order to start the pumps restore it 14 Check that the transducer is wired to the to the right measurement point 15 Check that the sensor is at the correct location according to the diagram and that it works properly 16 Check that the protective motor switch and the time relay are correctly set according to the Commissioning Report 17 Now run through all the contr...

Page 9: ...igned to operate automatically The Commissioning Record indicates the settings at which the system was set when it was commissioned Make sure that the settings on the thermostats controllers pressure switches and other adjustable components have not been altered by someone who lacks knowledge about how the system operates 3 See to it that the machine room or other component locations are kept clea...

Page 10: ... if required Faulty compressor Determine the fault Replace the compressor The low pressure switch switches out the compressor Too little refrigerant There is a leak in the system Seal the leak and charge with refrigerant No flow or poor flow across the evaporator Check the flow Check the static pressure in the expansion vessel Check the circulation pump Too high glycol content Check the glycol con...

Page 11: ...and the cooling perform ance of the system is at the same time poor the probable cause is that the system is leaking If you see one or two or just a few bubbles in the sight glass when the ma chine starts up and notice that it operates with reduced output or operates normally does not necessarily mean that the refrigerant volume is too low IF BUBBLES APPEAR IN THE SIGHT GLASS AND THE PERFORMANCE O...

Page 12: ...mpressor 2 VO Oil heater 3 GP High pressure switch 4 MU Measurement tapping of Schrader valve 5 KD Liquid cooling condenser 6 SG Sight glass 7 FT Drying filter 8 MU Measurement tapping of Schrader valve 9 VS Thermostatic expansion valve with external pressure compensation 10 EV Liquid cooler 11 MU Measurement tapping of Schrader valve 12 GP Low pressure switch ...

Page 13: ...0 40 40 40 40 40 40 40 Connection diameter dy mm 28 35 35 42 42 54 54 54 Rec cooling medium volume min l 287 431 556 359 432 556 467 556 Heating medium Water temp 31 39 C l s 0 66 0 98 1 28 1 64 1 95 2 56 3 22 3 83 Internal pressure in connection point kPa 35 35 35 35 35 35 35 35 Connection diameter dy mm 28 35 35 42 42 54 54 54 Refrigerant HFC 407C kg circuit 1 1 6 2 6 3 0 1 6 2 6 3 0 1 6 3 0 kg ...

Page 14: ...Page 14 Operation and Maintenance Instructions Envicooler 2001 03 09 Air handling with the focus on LCC ...

Page 15: ...Industriventilation Produkt AB Box 3103 SE 350 43 Växjö Sweden Phone 46 0 470 75 88 00 email info ivp skanska se www ivprodukt se Air handling with the focus on LCC 20010309E D ...

Reviews: