Page 9
Operation and maintenance
NEW EcoHeater
DSEH200301.01.EN
Continuous product development may give rise to specification changes without notice.
3.2 Function
General
The incoming water to the EcoHeater must be at least 20 °C to ensure the
operational safety of the EcoHeater.
Recovered energy is returned to the property's heating system.
max temp out = 60
˚
C
min temp in = 20
˚
C
max temp in = 53
˚
C
normal
∆
t = 7
˚
C
CP1
GT3
EcoHeater
Min 10 °C
Max 30 °C
Drain
CP2
GT5
GT6
GT7
GF1
F0
HP1
LT12
OP1
EV1
GT4
GT2 GP4
GP2
ET1
OT1
EP1
FF
C1
CT1
+2 °C
C1
Compressor, variable speed controlled
GT2
Temperature sensor extract air
Drain
Condensate drain, frost protected (for
outdoor configuration)
GT3
Temperature sensor outdoor air (north-
east location)
EP1
Low-pressure sensor cooling circuit
GT4
Temperature sensor exhaust air
ET1
Pressure sensor cooling circuit suction
gas
GT5
Temperature sensor water out
CT1
Temperature sensor compressor sump
GT6
Temperature sensor water in
LT12
Temperature sensor liquid line
OT1
Temperature sensor hot gas
EV1
Expansion valve, electronic
HP1
High-pressure switch
F0
Frequency inverter for compressor
OP1
High-pressure sensor cooling circuit
EA
Extract air fan, variable speed controlled
CP2
Circulation pump radiator circuit
GF1
Water flow sensor
CP1
Circulation pump heat pump
GP4
Pressure extract air duct
GT7
Temperature sensor radiator circuit (for
internal control only, not used for exter-
nal control 0 – 10 VDC).