LEVELING 

The Stockpot Range is equipped with legs. Turn the feet at the bottom of the legs in or 
out to level the Stockpot Range in the final installed location.  

VENTILATION HOOD 

The stockpot should be installed under a suitable ventilation hood. For safe operation and 
proper ventilation, keep the space between the stockpot and vent hood free from any 
obstructions. 

GAS CONNECTION 

The data plate on the lower right side of the charbroiler indicates the type of gas your unit 
is equipped to burn.  DO NOT connect to any other gas type. 

CAUTION:  All gas supply connections and any pipe joint compound must be 
resistant to the action of propane. 

Purge the supply line to clean out any dust, dirt, or any foreign matter before connecting 
the line to the unit. 

Codes require that a gas shut-off valve be installed in the gas line ahead of the 
charbroiler.  The gas supply line must be at least the equivalent of ¾” iron pipe.  72-inch 
units should be connected to the gas supply on both the left and right sides to provide 
adequate gas flow.   

A pressure regulator is supplied and must be installed outside of the broiler when making 
the gas supply connection.  Standard orifices are set for 5"WC (Water Column) for 
Natural Gas — 10"WC (Water Column) for Propane.  Use the 

1

/

8

” pipe tap on the burner 

manifold for checking pressure.  Make sure the gas piping is clean and free of 
obstructions, dirt, and piping compound. 

An adequate gas supply is necessary.  Undersized or low pressure lines will restrict the 
volume of gas required for satisfactory performance.  A maximum supply pressure of 7" 
W.C. for natural gas and 11" W.C. for propane gas is recommended.  With all units 
operating simultaneously, the manifold pressure on all units should not show any 
appreciable drop.   

When testing the gas supply piping system, if test pressures exceed ½ psig (3.45 kPa), 
the charbroiler and its individual shutoff valve must be disconnected from the gas supply 
piping system.  When test pressures are ½ psig (3.45 kPa) or less, the charbroiler must 
be isolated from the gas supply piping system by closing its individual manual shut-off 
valve during any pressure testing of the system. 

WARNING

:  PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR 

LEAKS.  USE SOAP AND WATER SOLUTION.  DO NOT USE AN OPEN FLAME. 

 

Summary of Contents for ML-052822

Page 1: ...TAIN THIS MANUAL FOR FUTURE USE FORM F 36951 04 07 INSTALLATION OPERATION MANUAL FOR Stockpot Range MODELS MLS VSP100 ML 052822 VSP200 ML 052823 VSP200F ML 769292 www vulcanhart com MODELS MLS WSPR1 ML 760600 WSPR2 ML 760601 WSPR2F ML 769292 www wolfrange com VSP100 WSPR2F ...

Page 2: ...PORTANT IN THE EVENT A GAS ODOR IS DETECTED SHUT DOWN UNITS AT MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE INJURY OR DEATH READ THE I...

Page 3: ...the clearance dimensions see below agree with the specifications on the rating plate which is located at the back of the stockpot LOCATION The installation location must be kept free and clear of combustibles Do not obstruct the flow of combustion and ventilation air DO NOT install the stockpot adjacent to open burners or fryers Sufficient air should be allowed to enter the room to compensate for ...

Page 4: ...tion Association Batterymarch Park Quincy MA 02269 In Canada 1 Local codes 2 CAN CSA B149 1 Natural Gas Installation latest edition 3 CAN CSA B149 2 Propane Installation Code latest edition available from the Canadian Gas Association 178 Rexdale Blvd Etobicoke Ontario Canada M9W 1R3 GAS PRESSURE REGULATOR INSTALLATION Gas regulator pressure is preset at 5 Water Column W C for natural gas and 10 W ...

Page 5: ... A pressure regulator is supplied and must be installed outside of the broiler when making the gas supply connection Standard orifices are set for 5 WC Water Column for Natural Gas 10 WC Water Column for Propane Use the 1 8 pipe tap on the burner manifold for checking pressure Make sure the gas piping is clean and free of obstructions dirt and piping compound An adequate gas supply is necessary Un...

Page 6: ...xibility With one burner off and the second burner set low up to both burners full on you can move from low simmer on up to 110 000 BTU hr input Fig 1 Fig 2 LIGHTING INSTRUCTIONS 1 Turn all burner valves to OFF position and wait 5 minutes 2 Turn gas shutoff valve ON 3 Light standing pilot with a lit taper Adjust pilot to high flame if necessary by turning pilot valve adjusting screw see Fig 1 coun...

Page 7: ... STOCKPOT RANGE AND ITS PARTS ARE HOT USE CARE WHEN OPERATING CLEANING OR SERVICING SERVICE Contact your local Service Agency for any repairs or adjustments needed on this equipment TROUBLESHOOTING PROBLEM POSSIBLE CAUSES Pilot Outage 1 Pilot flame too low 2 Restriction in pilot orifice 3 Restriction in pilot valve Improper burner combustion Improper ventilation Poor Ignition 1 Insufficient gas in...

Reviews: