Settings
6 720 802 419 (2012/06) en
56
16.3 Holiday
During holidays (absence), the heating can, for example, be kept at a
lower or higher level and hot water production can be switched off.
Start
and
Stop date
,
Room temperature
and
Block hot water production
are
only displayed if the holiday function is activated.
> Circuit 1 and hot water
>> Activate holiday function
>> Start date
>> Stop date
B
Set start and stop date for the desired period. Format yyyy-mm-dd.
The period starts and ends at 00:00. Both the start and end date are
included in the period.
B
Terminate the period prematurely by indicating
No
in the menu
Activate holiday function
.
>> Room temperature
B
Set the room temperature that should apply to the circuit during the
period.
>> Copy to all heating circuits
>> Block hot water production
> Circuit 2, 3...
(optional)
>> Activate holiday function
>> Start date
>> Stop date
>> Room temperature
B
Set the values in the same way as for
Circuit 1 and hot water
.
16.4 Energy measurements
> Generated energy
This displays
Generated energy
in kWh divided into
Heating
and
Hot
water
.
> Consumption electric additional heat
This displays
Consumption electric additional heat
in kWh divided into
Heating
and
Hot water
.
Factory setting
No
Alternative
No/Yes
Table 95 Holiday function
Factory setting
17 °C
Lowest value
10 °C
Highest value
35 °C
Table 96 Room temperature, holiday
Factory setting
No
Alternative
Yes/No
Table 97 Copy circuits
Factory setting
No
Alternative
Yes/No
Table 98 Block hot water
Energy is measured per compressor; the calculated
results are added prior to being displayed.