2.2. Control System
The following equipment variants can be supplied:
1. Altima
• Visual function control of UV lamp by transparent lamp connection
• Control box which can be fastened easily (assembly on the wall or reactor)
2. Proxima
• As Altima variant
• Possibility of connecting a solenoid valve which allows water flow only in the case
of a shining UV lamp
• Control of the solenoid valve by a micro-controller
• Remaining life of UV lamp shown on the display
• Visual and acoustic alarm in the case of lamp failure
3. Maxima
• As Proxima variant
• A UV sensor which continuously monitors the intensity, switches off the solenoid
valve when the minimum intensity is not reached and emits a visual and acoustic
alarm. The intensity is shown on the display.