6.5 Signalling/Relay contacts
A two-color LED, red/green, is integrated for the signalling
of operational and error states
Function
LED
Operation
Fault
Contact
Contact
51-64
51-54
Pump OFF
off
off
off
Pump running in sector
A
lit green
on
off
Pump running in sector
B
flashes green
on
off
irregularly**
Pump running in sector
C
flashes green
on
off
regularly*
Electronics fautes
flash red
off
1)
on
1)
regularly
Night-time reduction
flash
on
off
green/red
Pump blocked
lit red
off
1)
on
1)
* = flashing regularly:
1 s on/ 1 s off
** = flashing irregularly:
1.5 s on/ 0.5 s off/ 0.5 s on/ 0.5 s off
1)
= after 1,5 min.