LXE 326, LXE 403 LXE 504
HXE 402-1
LXED 403
LXED 504
HXED 402-1
Nominal current Control
0,2 … 0,9 A
0,4 … 1,3 A
0,45 ... 2 A
min.
0,2 A
0,4 A
0,6 A
Output
Control
32 ... 200 W
90 ... 310 W
80 ... 450 W
min.
30 W
90 W
110 W
Capacitor fitted
8
µ
F, 400 V
8
µ
F, 400 V
10
µ
F, 400 V
english
39
The electrical connection must be made by an expert.
I.E.E. regulations must be complied with.
Please observe NIN (CENELEC) regulations.
5. Electrical connection
An all-pole disconnecting device, with a minimum contact
gap of 3 mm, must be connected to the motor.
In the case of higher water temperatures (over 80 °C), use an
appropriate heat-resistant connecting line.
Be sure to provide protection against dripping water and a mains
lead cleat at the cable inlet to the connection box (gland)!
Preliminary fuse:
max. 10 A, delay-action
Wire cross section: 1,5 mm
2
.
Starting current:
= rated current.
The electrical connection must be made in accordance with the
data plate. To simplify later replacement, the electrical connection
should be looped. It is important to check that the electrical dates
given on the compalison of types agrees with the local current
supply.
Note:
Particular attention must be given to the protective ground
terminal. The protective ground must be longer than the pole
conductor (danger of tearing off).
Supply voltage:
1
×
230 V +6%/–10%, 50 Hz, PE
Mains connection 1
×
230 V
Earth
L
Live
N
Neutral
Note:
Before carrying out any operations in the terminal box, the power
supply to the pump must be switched off.
5.1 Connecting terminals
If the connection is made incorrectly and the voltage
is wrong the motor will be damaged!
If the voltage is wrong, the motor will be damaged.
Before carrying out any work in the terminal box,
the power supply to the pump must be switched off.
Warning
LXE_HXE 03.11.2006 8:36 Uhr Seite 39