ITS Heat Pumps
Domestic Heat Pump Product Manual
Page 13 of 14
PP1
PP1 Tank water temperature sensor failure or connection problem.
PP2
PP2 Outlet water temperature sensor failure
PP3
PP3 Coil temperature sensor failure
PP4
PP4 Return gas temperature sensor failure
PP5
PP5 Ambient temperature sensor failure
PP6
PP6 Discharge gas over temperature protection
PP7
PP7 Anti-freeze protection
PP8
PP8 Discharge gas sensor failure
EE1
EE1 High working gas pressure – water flow restriction
EE2
EE2 Low working pressure – possible gas leak
EE3
EE3 Water flow failure (swimming pool heat pumps)
EE4
EE4 Phase protection (3 phase models only)
Defrost Indication
Busy defrosting
EE8
Communication failure between controller and display.
9
STANDARD CONTROLLER PARAMETERS
Parameter
Description
Range
Default
parameter 0
Return water temperature to start electrical heater
0-50°C
15°C
parameter 1
Setting desired water temperature in water tank.
10-60°C
53°C
parameter 2
Defrosting cycle
10-90min
45min
parameter 3
System Coil Temperature point to start defrosting
0 - -30°C
-7
parameter 4
System Coil Temperature point to stop defrosting
2-30°C
13°C
parameter 5
Defrosting cycle
1-12Min
8Min
parameter 6
Heat Pump running controlled by (o-inflowing water temp. 1 – out flowing water temp.0
0-1
0
parameter 7
Memory recovery ( Auto restart) after power failure
0-1
1 (yes)
parameter 8
Electronic expansion valve control(manual / automatic)
0-1
1 (yes)
parameter 9
Different working mode of water pump
0-1
1
Description
Range
Default
parameter A
Fan motor working mode 0=daytime working mode 1=night time working mode
0-1
0
parameter B
Target superheat setting
F-F
-3 to +3
parameter C
Manual control of EE valve
10-50
35
parameter D
Temperature to start the electric heater (ambient)
-5 ~ 10°C
5
parameter E
Water temp. difference setting for heat pump restart-up
2 ~ 15°C
3
parameter F
Inflowing water temperature
-9 ~ 99°C
measured
parameter 10
Out flowing water temperature
-9 ~ 99°C
measured
parameter 11
System Coil temperature
-9 ~ 99°C
measured
parameter 12
Return Gas temperature
-9 ~ 99°C
measured
parameter 13
Ambient temperature
-9 ~ 99°C
measured
parameter 14
Discharge Gas temperature
0-C7
measured
parameter 15
Real time paces of EE valve
10-50
measured