Input / Output Settings SW2
DIP
Switch
Function
ON
OFF
Default
Setting
2-1
Sensor A or Motor A synchronous
Synchronization signal
Sensor signal
ON
2-2
Sensor B or Motor B synchronous
Synchronization signal
Sensor signal
ON
2-3
Motor A input function
Forcible run
Forcible stop
ON
2-4
Motor B input function
Forcible run
Forcible stop
ON
DIP switch 2-1 – Sensor A or Motor A synchronous output
•
Synchronous output (SYN A; ON) [Default]
o
Outputs a signal on CN4-5 when motor A runs
•
Sensor output (SEN A; OFF)
o
Outputs a signal on CN4-5 when sensor A is blocked
DIP switch 2-2 – Sensor B or Motor B synchronous output
•
Synchronous output (SYN B; ON) [Default]
o
Outputs a signal on CN4-6 when motor B runs
•
Sensor output (SEN B; OFF)
o
Outputs a signal on CN4-6 when sensor B is blocked
DIP switch 2-3 – Motor A input function
•
Forcible STOP (OFF)
o
Prevents an article from advancing downstream once motor A’s zone (while receiving the signal)
becomes occupied
•
Forcible RUN (ON) [Default]
o
Forces motor A’s zone to RUN (while receiving the signal) under these conditions:
This setting does not override accumulation logic
If the zone is already occupied and stopped, it will not RUN
RUN Hold timer (SW5) has been added to this input and setting to alleviate the need of an
external controller/timer with an infeed photo-sensor. Therefore, once an article clears the photo-
sensor connected to this input (CN4-5), zone A will continue to operate and allow the article to
reach the next zone’s photo-sensor.
DIP switch 2-4 – Motor B input function
•
Forcible STOP (OFF)
o
Prevents an article from advancing downstream once motor B’s zone (while receiving the signal)
becomes occupied
•
Forcible RUN (ON) [Default]
o
Forces motor B’s zone to RUN (while receiving the signal) under these conditions:
This setting does not override accumulation logic
If the zone is already occupied and stopped, it will not RUN
RUN Hold timer (SW5) has been added to this input and setting to alleviate the need of an
external controller/timer with an infeed photo-sensor. Therefore, once an article clears the photo-
sensor connected to this input (CN4-5), zone B will continue to operate and allow the article to
reach the next zone’s photo-sensor.