10. Technical data

Type designation

I/O-04HD-230V-16A

Article no.

80022464

Operating voltage

16-35V DC or 16-27V AC

Current consumption

200mA at 24V DC

Inputs

230V AC, input current each input 1.5mA at 230V

Minimum load of the contact

500mW, min. 10V, min. 5mA

Outputs

Relay contact:

- max. switching voltage 440V AC
- max. switching current 20A >> (terminal max. 16A !)
- mechanical lifetime 1.000.000 switching cycles

Load capacity:

- pure ohmic 16A
- bulbs 3500W (max. 30.000 switching cycles)
- fluorescent lamps uncompensated 3500W (max. 30.000 switching cycles)

fluorescent lamps compensated

 2500W/200uF (max. 30.000 switching cycles)

- HV-halogen 3500W (max. 30.000 switching cycles)
- LV-halogen via transformer 2000VA (max. 30.000 switching cycles)
- ECGs manufacturer dependent! Inrush current 100A <20ms

!! The inrush current of electronic ballasts (ECGs) is up to 100 times the nominal current !!

Subnet (RS-485)

max. 5.6V limited by Z-diodes

Dimensions

WxHxD 105x90x60mm DIN rail mounting (6 HP)

Weight

325g

Connection

screw terminals 2.5mm² pluggable

Operating temperature

-10°C to +50°C

Storage temperature

-25°C to +70°C

Humidity

0...85% r. h. non condensing

Protection class

in not installed state IP30

CE mark

yes

Parameterization

The ISYGLT ProgramDesigner offers a wide range of parameterization options:

• 

Definition of the functions in the operating modes: BUS operation, BUS failure, emergency operation

• 

Function assignment per output

• 

Synchronization conditions per output

• 

Definition of the 4 LEDs for feedback of the outputs

Summary of Contents for I/O-04HD-230V-16A

Page 1: ...www seebacher de Phone 49 0 80 41 77 77 6 Marktstrasse 57 83646 Bad T lz info seebacher de Fax 49 0 80 41 77 77 2 1 Technical Data Instruction Manual I O 04HD 230V 16A Article no 80022464 4 way Switc...

Page 2: ...e handed over to the device operator The operator will store the documents so that they can be made available if necessary 1 2 Symbols used Observe the following safety and other instructions in the m...

Page 3: ...rrors 2 Safety instructions Observe the following general safety instructions when installing and commissioning the device Assembly and installation of the ISYGLT module may only be carried out by a q...

Page 4: ...screws Assembly site The product can be installed in any position in a casing to be deter mined by the electrician distribution box switch cabinet Observe maximum ambient temperature Assembly steps Re...

Page 5: ...voltage Ub 0V 4 outputs 4 inputs on a common reference terminal 2 P COM connections subnet and operating voltage Design DIN rail mounted plastic housing light grey snap on on 35mm DIN rail 6 HP Speci...

Page 6: ...200uF max 30 000 switching cycles HV halogen 3500W max 30 000 switching cycles LV halogen via transformer 2000VA max 30 000 switching cycles ECGs manufacturer dependent Inrush current 100A 20ms The in...

Page 7: ...7 10 1 Pin assignment Ub Operating voltage 0V Operating voltage A Subnet BUS A RS 485 B Subnet BUS B RS 485 View Eing nge 230V Eing nge 230V AC A1 Output 1 C 1 Common for A1 A2 Output 2 C 2 Common for...

Page 8: ...n max 230V 16A per contact 24V 0V BUS A BUS B N N M N M L L L Important Connect all inputs with the same phase Otherwise destruction of the module 400V 1 2 K1 L N 010 230V AC input current per input 1...

Reviews: