10. Technical data
Type designation
I/O-04HD-230V-16A
Article no.
80022464
Operating voltage
16-35V DC or 16-27V AC
Current consumption
200mA at 24V DC
Inputs
230V AC, input current each input 1.5mA at 230V
Minimum load of the contact
500mW, min. 10V, min. 5mA
Outputs
Relay contact:
- max. switching voltage 440V AC
- max. switching current 20A >> (terminal max. 16A !)
- mechanical lifetime 1.000.000 switching cycles
Load capacity:
- pure ohmic 16A
- bulbs 3500W (max. 30.000 switching cycles)
- fluorescent lamps uncompensated 3500W (max. 30.000 switching cycles)
-
fluorescent lamps compensated
2500W/200uF (max. 30.000 switching cycles)
- HV-halogen 3500W (max. 30.000 switching cycles)
- LV-halogen via transformer 2000VA (max. 30.000 switching cycles)
- ECGs manufacturer dependent! Inrush current 100A <20ms
!! The inrush current of electronic ballasts (ECGs) is up to 100 times the nominal current !!
Subnet (RS-485)
max. 5.6V limited by Z-diodes
Dimensions
WxHxD 105x90x60mm DIN rail mounting (6 HP)
Weight
325g
Connection
screw terminals 2.5mm² pluggable
Operating temperature
-10°C to +50°C
Storage temperature
-25°C to +70°C
Humidity
0...85% r. h. non condensing
Protection class
in not installed state IP30
CE mark
yes
Parameterization
The ISYGLT ProgramDesigner offers a wide range of parameterization options:
•
Definition of the functions in the operating modes: BUS operation, BUS failure, emergency operation
•
Function assignment per output
•
Synchronization conditions per output
•
Definition of the 4 LEDs for feedback of the outputs