![Isokern MAGNUM 82028 Installation, Operation, Maintenance And Owner'S Manual Download Page 48](http://html1.mh-extra.com/html/isokern/magnum-82028/magnum-82028_installation-operation-maintenance-and-owners-manual_2093411048.webp)
48
Earthcore Industries
MAGNUM Series Fireplace
Attach the elbow to the chimney pipe, support or
other part. Using the offset chart, add chimney
sections between elbows. A Support Band or
plumbers strap is required for every 4-foot interval
between elbows to support the load
(Figure 54)
.
Attach the upper elbow to bring the chimney back
to vertical. See
TABLE 2
and
Figure 55
for offset
combinations – 2 offsets (4 elbows) maximum.
9.
For chase enclosures, install the chase top
cover (supplied by others) to the chase enclosure.
Cut a hole in the chase top cover the same
diameter as the base of the cone on the flashing.
Attach the Flashing to the top of the chase
cover, sealing with a non-hardening waterproof
sealant. Secure in place with screws or rivets
(Figure 58)
.
10.
Attach the storm collar around the chimney
above the screen of the flashing. Secure in place
with the locking tab and button. Seal around the
storm collar with a non-hardening waterproof
sealant. Attach the Termination Cap to the chimney
by sliding the male to female joint connection
together and secure in place with four (4) sheet
metal screws provided
(Figure 59)
.
11.
Termination:
NFPA 211, “Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel-
Burning Appliances,” states that chimneys shall
extend at least three feet above the highest point
where it passes through the roof of a building,
and at least two feet higher than any portion of a
building within ten feet
(Figure 60)
.
If the horizontal distance from the chimney edge to
the peak of the roof is greater than 10', a chimney
height reference point is established on the roof
surface 10' horizontally from the chimney edge.
The top of the chimney (point where exhaust
gases exit) must be at least 2' above this reference
point. In all cases, the chimney must terminate a
minimum of 3' above the highest point of the roof
opening.
(Figure 60)
The 10-foot rule is necessary in the interest of
safety and does not ensure smoke free operation.
Trees, building, adjoining rooflines, adverse wind
conditions, etc., may require a taller chimney
should a smoking problem exist.
ECO-STEEL Metal Chimney Installation
Screw Or
Rivet Straps
To Flashing
Chase
Cover
(Supplied by
Others)
Screw
Or Rivet
To Chase
Cover
Apply Sealant
Screw to
Chase
Chase
Chimney
Self-Tapping
Screws
Apply
Sealant
Flashing
Storm Collar
Termination
3 Feet Minimum
Above Roofline
2 Feet Above Any
Point Within
10 Feet Horizontally
FIGURE 58
FIGURE 59
FIGURE 60