Rough Framing Dimensions
FIGURE 12
FIGURE 13
DM
Chimney
Earthcore Industries
MAGNUM Series Fireplace
22
Typical Installation Framing Dimensions
MAGNUM
Width - A
Height - B
Depth - C
Model 28
38 ½”
61 ½”
29 ½”
Model 36
46” 71” 29 ½”
Model 42
52” 71” 29 ½”
Model 48
56” 71” 29 ½”
NOTES:
1.
“B” includes the 3”-thick base plate.
2.
“Raised hearth” requires additional rough opening height
at “B” equal to the height of the raised hearth detail.
3.
Rough framing dimension for width “A” allows for the
required 1½” clearance at the sides of the Fireplace.
4.
Rough framing dimension for depth “C” allows for the
required 1½” clearance at the back of the Fireplace. 29½"
is only for an interior wall as most exterior wall framing
have insulation, even if the wall is 2 x 6, the foam they
spray expands, so typically 31" is allowed on an exterior
wall
(Figure 12)
.
Corner Installation Framing Dimensions
The following chart of dimensions detail the positioning of
an MAGNUM Series fireplace in a corner. It also
details the positioning of DM chimney where it must turn
45° degrees, if alignment is needed to overhead framing
(Figure 13)
.
MAGNUM
A
B
C
D
Model 28
38 ½” 20” 26 ½” 68”
Model 36
46”
23 ½” 32”
73”
Model 42
52”
26 ½” 36”
77”
Model 48
56”
28 ½” 39”
80”
To turn flue 45°, first set starting inner liner onto the top
plate of the fireplace.
Next, set a DM outer casing onto the inner liner so that
the outer casing is at 45° to the firebox and square to the
overhead framing system. Run the vertical DM chimney
through the overhead framing.
Offset blocks can be used, if necessary, to align with over-
head framing before running the vertical DM chimney outer
casing and liner.
NOTE:
Support the third offset down to footings and at
each third offset block thereafter.