1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
MIN.
MIN.
MIN.
MIN.
MIN.
FACE OF WOOD
FRAMING
FACE OF WOOD
FRAMING
COMBUSTIBLE
FRAMING
33
Required Clearance to Combustible Framing
FIGURE 72
MAGNUM fireplaces are tested and listed for one and one-half inch (1-1/2”) clearance to uninsulated combustible framing
material at the firebox sides and back.
Installation and use practices that are beyond the control of the manufacturer* can result in situations where clearance
requirements (as determined through testing and as stated by the manufacturer) are not maintained due to construction subsequent to
the installation of the Isokern unit. It is the general contractor’s responsibility to assure that listed clearances to combustible framing
and to insulation are maintained throughout the construction of the project subsequent to the installation of the Isokern unit.
To avoid causing a fire resulting in damage to property, personal injury or loss of life, do not pack or fill the required air spaces with
insulation or other material. No material is allowed in these areas. (Figures 72 & 73)
*The manufacturer is not responsible for installation and use practices that are beyond the scope of the product as defined in the
product listing and in the installation manual.
FIGURE 73