Modbus TCP Slave Numeric Value component has the following slots:
Status
–
Point status,
Fault Cause
–
Fault cause description,
Description
–
Point description label up to 32 characters,
Address Format
–
Modbus addressing format: Modbus/Decimal
Address
–
Register address (from0 to 65535),
Data Type
–
Variable data type: Int, Sint, Long, Slong, Float
WARNING! Long, Slong and Float are 32bit and they use 2 registers
Register Type
–
Register type for Master Device: Holding Register
–
read/write, Input
Register
–
read only,
Trigger
–
Remote force Input value writing to controller Modbus table trigger (on rising
edge),
Out
–
Output slot, current value of device registry,
In
–
Input slot.
6.3
Modbus Folder
ModbusFolder is a component which groups and organizes Modbus points components.
Because ofSedona components name are limited to 7 characters, ModbusFolder has
Description Slot where we can us up to 32 characters.