iSMA-B-AAC20/Sedona Modbus
Version 1.3
www.gc5.pl
Page 31 / 55
Device Down
–
Device is not available,
Wrong address format
–
Incorrect address format according to address format setting slot,
Device disabled - Device is disabled,
Network disabled
–
Modbus Network is disabled.
Fault Cause
–
Fault cause description,
Fault Status
–
Point error status (true
–
point read/write error),
Address Format
–
Register address format, available options: Modbus, Decimal,
Address
–
Register address,
Data Type
–
Read/write registry data type, available options: Int
–
16-bits, Long
–
32-bits,
Float
–
32-bits float-point, SInt
–
16-bits with sing, Slong
–
32-bits with sing,
Poll Frequency
–
Reading poll frequency, available options: Fast, Normal, Slow,
Write Type
–
Writing mode, available options: COV
–
only on input change,
COV_PollFrequency
–
on input change and periodically, PollFrequency - only periodically,
Trigger
–
Remote force sending trigger (on rising edge),
Out
–
Output slot, current value of device registry,
In
–
Input slot.
5.4.5
Modbus TCP Numeric Multi Point
Modbus Async Numeric Milti Point is a component which is responsible for reading up to 8
registers from the device in one message. The component use 0x16 Modbus command The
component has Read action available under the right mouse button, which forces the reading
of the point.