iSMA-B-AAC20/Sedona Modbus
Version 1.3
www.gc5.pl
Page 35 / 55
6.1
Modbus TCP Slave Network
Modbus TCP Slave is always enable and to read controller registers it doesn’t have to be
configured. Modbus TCP Slave network is use only for changing parameters (parameters can
by changed also from controller configuration web page) and to set up user registers.
Figure 17 - Modbus TCP Slave network component
Modbus TCP Slave Network has the following slots:
Status
–
Network status,
Fault Cause
–
Fault cause description,
Modbus TCP Port
–
Modbus TCP Port number (default 502),
Modbus Device Address
–
Controller Modbus address,
Watchdog Time
–
Time between receive valid messages after which controller will set
default values on outputs, value 0 disable this function.
6.2
Modbus TCP Slave data points
Modbus TCP Slave data points are served by two components placed under
ModbusTcpSlaveNetwork component: