Tech Setup Steps
LCD Will Show
Adjustment Options
Default
Heating
Swing*
The swing setting,
often called “cycle rate”,
“differential” or “antici-
pation”, is adjustable. A
smaller swing setting
will cause more frequent
cycles and a larger swing
setting will cause fewer
cycles.
Heat
Swing
The heating swing
setting is adjustable
from 0.2° to 2°. For
example: A swing
setting of 0.4° will
turn the heating on at
approximately 0.4° be-
low the setpoint and
turn the heating off
at approximately 0.4°
above the setpoint.
Heat
Swing
Heating
Temperature
Setpoint
Limit
This feature allows you
to set a maximum heat
setpoint value. The
setpoint temperature
cannot be raised above
this value.
Use the “+” or “-” key
to set the maximum
temperature setpoint:
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
Cooling
Temperature
Setpoint
Limit
This feature allows you
to set a maximum cool
setpoint value. The
setpoint temperature
cannot be raised above
this value.
Use the “+” or “-” key
to set the maximum
temperature setpoint:
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
F or C
Select F for Fahrenheit
temperature read out.
Select C for Celsius tem-
perature read out.
Use the “+” or “-”
key to select F for
Fahrenheit or C for
Celsius.
* The second stage of heat will turn on at 2x the swing setting. The second stage will turn off when
1x the swing is reached. For example, if the swing setting is 0.8° for heating and the thermostat is
set at 70 °F, the first stage will turn on at approximately 69.2 °F. The second stage will turn on at
68.4 °F and the first will turn off at 70.8 °F.