Tech Setup Steps
LCD Will Show
Adjustment Options
Default
Room
Temperature
Calibration
This feature allows the
installer to change the
calibration of the room
temperature display.
For example, if the
thermostat reads 70°
and you would like it to
read 72°, then 2.
You can adjust the
room temperature
display to read up to
4˚ above or below
the factory calibrated
reading.
Pair
Transmitter and receiver
pair code
Press and hold “+” for
3 seconds until “LE”
is flashed, then release
F or C
Select for F for Fahren-
heit temperature read
out. Select C for Celsius
temperature read out.
F for Fahrenheit
C for Celsius
Compressor
Short Cycle
Delay
The compressor short
cycle delay protects the
compressor from short
cycling. This feature
will not allow the
compressor to be turned
on for 5 minutes after it
was last turned off.
Selecting ON will not
allow the compressor
to be turned on for 5
minutes after the last
time the compressor
was switched off.
Select OFF to remove
this delay.
Change Over
Value Selec-
tion*
Select 0 for a change-
over valve that energizes
in cooling. Select b for
a changeover valve that
energizes in heating.
0 for cooling
changeover valve.
b for heating
changeover valve.
Heat Pump
When turned on the
thermostat will operate
a heat pump. Y will be
the first stage of heat
& cool, W will be the
second stage of heat.
OFF configures the
thermostat for non
heat pump systems.
ON configures the
thermostat for heat
pump systems.
Heating
Temperature
Setpoint
Limit
This feature allows you
to set a maximum heat
setpoint value. The
setpoint temperature
cannot be raised above
this value.
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
Cooling
Temperature
Setpoint
Limit
This feature allows you
to set a maximum cool
setpoint value. The
setpoint temperature
cannot be raised above
this value.
44.0˚ - 90.0˚ F
7.0˚ - 32.0˚ C
* All Islandaire units should always be set to b
10
Technician Setup Menu