Islandaire 6041206 Installation And Operation Manual Download Page 12

Tech Setup Steps

LCD Will Show

Adjustment Options

Default

Room 

Temperature 

Calibration

This feature allows the 

installer to change the 

calibration of the room 

temperature display.  

For example, if the 

thermostat reads 70° 

and you would like it to 

read 72°, then 2.

You can adjust the 

room temperature 

display to read up to 

4˚ above or below 

the factory calibrated 

reading.

Pair

Transmitter and receiver 

pair code

Press and hold “+” for 

3 seconds until “LE” 

is flashed, then release

F or C

Select for F for Fahren-

heit temperature read 

out. Select C for Celsius 

temperature read out.

F for Fahrenheit 

C for Celsius

Compressor 

Short Cycle 

Delay

The compressor short 

cycle delay protects the 

compressor from short 

cycling. This feature 

will not allow the 

compressor to be turned 

on for 5 minutes after it 

was last turned off.

Selecting ON will not 

allow the compressor 

to be turned on for 5 

minutes after the last 

time the compressor 

was switched off. 

Select OFF to remove 

this delay.

Change Over 

Value Selec-

tion*

Select 0 for a change-

over valve that energizes 

in cooling. Select b for 

a changeover valve that 

energizes in heating.

0 for cooling 

changeover valve. 

b for heating 

changeover valve.

Heat Pump

When turned on the 

thermostat will operate 

a heat pump. Y will be 

the first stage of heat 

& cool, W will be the 

second stage of heat.

OFF configures the 

thermostat for non 

heat pump systems. 

ON configures the 

thermostat for heat 

pump systems.

Heating 

Temperature 

Setpoint 

Limit

This feature allows you 

to set a maximum heat 

setpoint value. The 

setpoint temperature 

cannot be raised above 

this value.

44.0˚ - 90.0˚ F

7.0˚ - 32.0˚ C

Cooling 

Temperature 

Setpoint 

Limit

This feature allows you 

to set a maximum cool 

setpoint value. The 

setpoint temperature 

cannot be raised above 

this value.

44.0˚ - 90.0˚ F

7.0˚ - 32.0˚ C

* All Islandaire units should always be set to b

10

Technician Setup Menu

Summary of Contents for 6041206

Page 1: ...NON PROGRAMMABLE WIRELESS THERMOSTAT 6041206 Installation and Operation Manual 6140429 Rev 08 24 20...

Page 2: ......

Page 3: ...e Yes Geothermal Yes Table of Contents page Installation Tips 2 3 Thermostat Quick Reference 4 Wiring 5 6 Wiring Diagrams 7 8 Technician Setup 9 10 Swing Setting 11 Specifications 12 Thermostat Applic...

Page 4: ...e of the building Do not install thermostat in locations Close to hot or cold air ducts That are in direct sunlight On an outside wall In areas that do not require conditioning Where there are dead sp...

Page 5: ...nstallation 1 5V AAA 1 5V AAA Battery installation is optional if thermostat is hardwired RH and C terminal connected to 24V power Important High quality alkaline batteries are recommended Rechargeabl...

Page 6: ...n indicator is shown 1 2 3 4 Press the or buttons to select the desired room temperature LCD 1 AUTO will turn the fan on only when the heating or cooling system is on Select LOW or HIGH for the fan to...

Page 7: ...s Terminal 1 Heat 1 Cool Conventional System 1 Heat 1 Cool Heat Pump System 2 Heat 1 Cool Heat Pump System R Transformer power Transformer power Transformer power C Transformer common Transformer comm...

Page 8: ...nnect the power before beginning to install this product can cause electrical shock or equipment damage Wire Specifications Use shielded or non shielded 18 22 gauge thermostat wire Warning All compone...

Page 9: ...2 R Y W C GL GH Typical 1H 1C Conventional System 2 Speed Fan 1 2 3 4 Power supply Jumper not supplied to connect GL and GH terminals The Aux Heat Relay is energized as the second stage of heat Typic...

Page 10: ...L GH Typical 1H 1C Heat Pump System 2 Speed Fan Typical 2H 1C Heat Pump System 2 Speed Fan 1 2 3 Power supply Cap o W Thermostat must be set to B on all Heat Pump Systems 2 Note Most PTAC systems supp...

Page 11: ...r systems that control the fan during a call for heat put the switch in the GAS position Technician Setup Menu 1 Set the thermostat system switch to OFF 2 To enter Tech Setup Menu press and hold and t...

Page 12: ...ill not allow the compressor to be turned on for 5 minutes after the last time the compressor was switched off Select OFF to remove this delay Change Over Value Selec tion Select 0 for a change over v...

Page 13: ...ing on at approximately 0 5 above the setpoint and turn the heating off at approximately 0 5 below the setpoint Swing Setting The second stage of heat will turn on at 2x the swing setting The second s...

Page 14: ...e or differential Heating is adjustable from 0 2 to 2 0 Cooling is adjustable from 0 2 to 2 0 Power Source 18 to 30 VAC NEC Class II 50 60 Hz for hardware Battery power from 2 AAA Alkaline batteries O...

Page 15: ...13 Specifications 3 86 1 1 1 2 375 4 72 3 00 1 75 1 125...

Page 16: ...Installation and Operation Manual...

Reviews: