4
Electrical Ground:
The HAG series generators are a low voltage output system (48volt,
3ph, 240hz loaded). As specified in the National Electrical Code
(NEC) part 250.21 & 250.22 any “stand alone” low voltage system
under 50 volts AC (loaded) does not require a ground.
If an inspector on a specific job site “request” a grounded system,
the HAG series units are equipped with a “ground lug” connection
located on the side of the electrical control panel. Simple attach a
length of appropriate wire to the ground lug and attach to a ground
connection as deemed acceptable to the inspector.