background image

- 6 -

If  a  load  R  is  grounded  to  a  local  loop 
ground LG, the available common mode 
voltage  CMV  is  limited  on  the  positive 
side  by  the  unit’s  internal  power  supply 
and on the negative side by the 600 mW 
power dissipation limit of an output tran-
sistor.  The  diagram  to  the  right  shows 
allowable  CMV  as  a  function  of  output 
load  resistance  R.  For  example,  with  a 
250  ohm  load,  CMV  can  range  from 
-13V  to  +17V.  With  a  500  ohm  load,
CMV can range from  -18V to +12V. The
unit will not work correctly if CMV limits
are  exceed  or  load  resistance  is  greater
than  600 ohms.

8. SETTING & CALIBRATION

Zero and span of the four output loops (

L1

L2

L3

L4

) are set be means 

of precision 25-turn potentiometers marked 

Z

 (for zero) and 

S

 (for span) 

on  the  front  panel.  The  unit  is  factory  jumpered  and  calibrated  so  that 
4-20 mA in produces 4-20 mA out on all output channels.

To set or calibrate an output channel, apply the low input signal (4 mA, 0V 
or  1V)  which  should  produce  the  4  mA  low  output.  Measure  the  actual 
output (e.g., 4.218 mA). Then apply the high  input signal (20  mA,  5V or 
10V)  which  should  produce  the  20  mA  high  output.  Adjust  the 

S

  poten-

tiometer  until  actual  output  current  equals  the  just-measured  low  output 
plus 16 mA (e.g., 4.218 mA + 16 mA = 20.218 mA). Then reapply the low 
input  which  should  produce  a  4  mA  output,  and  adjust  the 

Z

  poten-

tiometer until the actual output current equals 4.000 mA.  

Since electronic components may change as they age, annual recalibration 
of the output channels is recommended using the 

Z

 and 

S

 potentiometers. 

The input channel does not require calibration. 

Summary of Contents for QLS-1

Page 1: ...d Output 4 20 mA Current Loop Splitter Retransmitter With 10V common mode isolation between input outputs ISE Inc 10100 Royalton Rd Cleveland OH 44133 USA Tel 440 237 3200 Fax 440 237 1744 Website ISE...

Page 2: ...loop loose their 4 20 mA signal The transmitter voltage compliance limit may be exceeded since the voltage drops across loads in series are additive Also the 4 20 mA signal to each load device cannot...

Page 3: ...48 Vdc power connector is colored Black This unit has no power switch It will be in operation as soon as power is applied To avoid dangers of electrocution and or short circuit do not attempt to open...

Page 4: ...al input connector on the circuit board The factory default input setting is 4 20 mA To change jumpers remove power then open the case by removing the screws at the four corners of the case Store the...

Page 5: ...y tied to signal ground SG which can be floating or be connected to earth ground Grounded loads Any output load R can be connected to a local loop ground LG instead of current return The loop grounds...

Page 6: ...marked Z for zero and S for span on the front panel The unit is factory jumpered and calibrated so that 4 20 mA in produces 4 20 mA out on all output channels To set or calibrate an output channel app...

Page 7: ...error at 23 C Span Tempco 10 ppm C 0 16 A C typical 25 ppm C 0 4 A C max AC Rejection 90 dB from DC to 60 Hz Response Speed 2 ms risetime 7 ms settling time to 0 1 of final value Current Test Point 10...

Page 8: ...Mishandling or abuse The warranty set forth above is exclusive and no other warranty whether written or oral is expressed or implied Laurel specifically disclaims implied warranties of merchantabilit...

Reviews: