Power supply Connection
Chassis Ground Connection
The iSC2 chassis ground connection, located next to the terminal block, uses a #6-32 Screw. We
recommend terminating the ground connection using a #6 ring lug, and a torque setting of 15 in.lbs
(1.7Nm).
Configuring the Device
The ISC2 can be configured using the Mode DIP switch located on the right side off the enclosure.
The DIP switches are shown in Figure 8. Using the switches one can change the operating mode
of the ISC2.
100-240VAC rated equipment: A 250VAC appropriately rated circuit
breaker must be installed.
Equipment must be installed according to the applicable country wiring
codes.
88-370VDC rated equipment: A 370VDC appropriately rated circuit breaker
must be installed.
A circuit breaker is not required for DC power supply voltages of 9-48VDC.
Equipment must be installed according to the applicable country wiring
codes.