14
11) L ON Point Setting
This option determines the “ ON” point for L switched output
- Setting Range : SLM800S : 0.35~8m
- SLM1200S : 0.5~12m
12) L OFF Point Setting
This option determines the “ OFF” point for L switched output
- Setting Range : SLM800S : 0.35~8m
- SLM1200S : 0.5~12m
.
13) LL ON Point Setting
This option determines the low limit “ON” point for LL relay
- Setting Range : SLM800S : 0.35~8m
SLM1200S : 0.5-12m
14) LL OFF Point Setting
This option determines the low limit “OFF” point for LL relay
- Setting Range : SLM800S : 0.35~8m
SLM1200S : 0.5-12m
Important Information
The value of
HH relay ON point
should be higher than
OFF point
and this function is used for high limit.
The value of
LL relay ON point
should be lower than
OFF point
and this function is used for low limit
H, L relay are used for
pump control, draining control, high and low liquid level warning, etc.
at user’s need.
L ON POINT SET
ON : 2.00m
L OFF POINT SET
OFF : 3.00m
LL ON POINT SET
ON : 1.00m
LL OFF POINT SET
OFF : 2.00m