IronStrike Ravenna RDV33 IPI Installation And Operation Manual Download Page 39

39

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SAFETY / LISTING LABEL - Ravenna IPI

 

Ravenna™ IPI

MANUFACTURED BY:

INNOVATIVE HEARTH PRODUCTS

1502 14TH ST NW

AUBURN, WA., USA 98001

 

RDV IPI

SERIAL

 NO.

VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUEL

CONFORMS TO ANSI Z21.88-2014/CSA 2.33-2014 AND CAN/CGA-2.17-M91 (R2009).

THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY.  IF NOT, FOLLOW THE CURRENT ANSI Z223.1/NFPA 

54-LATEST EDITION (USA) OR CAN/CGA  B149.1-LATEST EDITION (CANADA). THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE 

WITH THE MANUFACTURER’S INSTALLATION INSTRUCTION. FOR INSTALLATION IN SOLID FUEL BURNING FIREPLACES ONLY - MASONRY 

OR FACTORY BUILT.  THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE WITH AIR FILTERS. 

THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE AND MAY BE INSTALLED IN AN 

AFTERMARKET, PERMANENTLY LOCATED, MANUFACTURED (MOBILE) HOME WHERE NOT PROHIBITED BY LOCAL CODES. SEE OWNER’S 

MANUAL FOR DETAILS. THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES UNLESS A CERTIFIED KIT IS USED.
DANGER: RISK OF ELECTRICAL SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT.

IF ELECTRICALLY CONNECTED, CONNECTIONS AND GROUNDING MUST BE IN ACCORDANCE WITH LOCAL CODES, IF ANY. IF NOT, 

FOLLOW THE CURRENT NATIONAL ELECTRICAL CODE ANSI/NFPA 70-LATEST EDITION (USA) OR CSA C22.1-LATEST EDITION (CANADA).

FACTORY EQUIPPED FOR NATURAL GAS. IF CONTROL PANEL CONTRADICTS THIS LABEL, UNIT FUEL TYPE HAS BEEN CONVERTED.

MINIMUM CLEARANCES

WARNING: IF UNIT IS CONVERTED TO AN RDV40 IPI FROM AN RDV33 IPI ENSURE THAT THE 

CLEARANCES TO COMBUSTIBLES ARE CORRECT FOR RDV40 IPI.

RATINGS

Ravenna 40 IPI  (RDV40 IPI)

Ravenna 33 IPI (RDV33 IPI)

For use only with 

barrier Part No. J7510 

(Contemporary Face) 

or Part No. J7511 (Cast 

Pillar Face). Follow 

installation instructions.

NATURAL GAS

LP GAS

NATURAL GAS

LP GAS

MAX/MIN INPUT BTUH 0-2,000 FT (0-610 M)*

40,000/28,000

37,500/26,000

33,000/24,000

33,000/24,000

MANIFOLD PRESSURE (IN. WC)

3.5

10.0

3.5

10.0

MIN. INLET PRESSURE (IN. WC)

5.0

10.5

5.0

10.5

ORIFICE (DMS) 0-2,000 FT (0-610 M)*

1/8”

#49

#36

#51

*UNIT FACTORY EQUIPPED FOR 0-2000 FT/0-610 M, IN CANADA 0-4500 FT/0-1370 M. ELECTRICAL RATING: 120 VAC, 60 HZ, LESS THAN 2 AMPS

CHIMNEY - USE 3" (76 MM) GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635.  

THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDANCE WITH THE MANUFACTURER’S 

INSTALLATION INSTRUCTIONS.

FOR ALTITUDES ABOVE 2,000 FT/610M (IN CANADA 4500 FT/1370M) DE-RATE THE APPLIANCE BY FOUR (4)% FOR EVERY 1,000 FT (305 M).

CAUTION:

 HOT WHILE IN OPERATION. DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP 

CHILDREN, CLOTHING, FURNITURE, GASOLINE AND OTHER LIQUIDS HAVING FLAMMABLE VAPORS AWAY. 

KEEP BURNER AND CONTROL COMPARTMENT CLEAN. SEE INSTALLATION AND OPERATING INSTRUCTIONS 

ACCOMPANYING APPLIANCE. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS APPLIANCE ONLY. DO NOT 

OPERATE THE APPLIANCE WITH GLASS REMOVED, CRACKED OR BROKEN. REPLACEMENT OF THE PANEL(S) 

SHOULD BE DONE BY A LICENSED OR QUALIFIED PERSON.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE 

INJURY OR PROPERTY DAMAGE. REFER TO THE OWNER’S INFORMATION MANUAL PROVIDED WITH THIS 

APPLIANCE. FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER, SERVICE 

AGENCY OR GAS SUPPLIER.

DO NOT REMOVE OR COVER THIS LABEL

Part No. 900377-00  Rev. 0, 12/2014

IGN _____

DATE OF MANUFACTURE / DATE DE FABRICATION

2014

2016

2017

2015

JAN

FEB MAR

APR MAY

JUN

JUL

AUG SEP

OCT

NOV DEC

MODEL

Note: Hearth protection to be min. 

3/8” (10mm) thick non-combustible 

or equivalent, with a k factor of .84.

A

D

B

E

C

CL

MANTEL

TRIM

MINIMUM FIREPLACE SIZES REQUIRED

 ....................

  RDV40 IPI 

RDV33 IPI

Front Opening ...................................................................  31.50” (800mm) 

31.50” (800mm)

Height .................................................................................  19.50” (495mm) 

19.50” (495mm)

Rear Width  ........................................................................  18.00” (457mm) 

18.00” (457mm)

Depth  .................................................................................  16.00” (406mm) 

16.00” (406mm)

MINIMUM CLEARANCES TO COMBUSTIBLES

  A = Top Facing to Bottom of Appliance .....................  35.5" (902mm) 

31.5" (800mm)

  B = Side Facing or Side Wall to Center of Glass ......  25.5" (648mm) 

25.5" (648mm)

* C = 10.5” (267mm) Mantel  to Bottom of Appliance .  43" (1092mm) 

39" (991mm)

HEARTH PROTECTION

  D = Vertical Distance from base of appliance       0"              2”              4”                0"              2”              4”

   to  Hearth Extension .......................................... (0mm)    (51mm)   (102mm)     (0mm)      (51mm)   (102mm) 

 

  E = Minimum Horizontal Distance 

   14"            10”              0”                13"           10”             0”

   from Front of Appliance ..................................  (356mm)  (254mm)   (0mm)      (330mm)  (254mm)    (0mm)

MANTEL

FACING

*See owner’s manual for additional mantel clearances and options.

Report No. 14-192

C

US

Summary of Contents for Ravenna RDV33 IPI

Page 1: ...ly call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a...

Page 2: ...O CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact ac...

Page 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Page 4: ...t Leveling 14 Fan Control Module Switch RDV 33 40 TCC models only 15 Installation 15 21 Venting Installation 15 Zero Clearance Fireplace Installation 17 USING THIS MANUAL Please read and carefully fol...

Page 5: ...ls viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une ba...

Page 6: ...ing es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor de control en el panel de control del artefacto verifique que el interruptor opera el artefa...

Page 7: ...pareil Figure A Choisissezlalanguequiestprincipalementparl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour limi...

Page 8: ...se or anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the...

Page 9: ...ver use solid fuels such as wood paper cardboard coal or any flammable liquids etc in this appliance Plated surfaces must be cleaned with glass cleaner and a clean soft cloth before firing the first t...

Page 10: ...ural gas or propane Is NOT for use with solid fuels Is approved for sitting rooms and or bedrooms This appliance is suitable for installation into masonry or factory built fireplaces Fireplace Require...

Page 11: ...a nationally recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified to ANSI Z21 88 CS...

Page 12: ...rmation This appliance comes from the factory equipped to burn natural gas at a specified elevation Only IHP conversion kits can be used to convert from NG to LP or LP to NG Contact your IHP dealer fo...

Page 13: ...A 31 1 2 800mm Front Opening Width B 19 1 2 495mm Height C 18 457mm Rear Width D 16 406mm Fireplace Depth Top View Left Side View Right Side View Front View A B C D Figure 3 Minimum Fireplace Cavity...

Page 14: ...screws Repeat these steps for each adjusting leg Facing and Mantel Clearances Please note that the RDV33 IPI TCC mantel clearances are 4 less than the RDV40 IPI TCC mantel clearances as shown in Figu...

Page 15: ...tructions for installation and vent termination These appliances are approved for use with the following vent kits Amerivent Flex Liner 3 X 35 3AFL 35 Adaptor w Flashing 4DCAT33 Termination Cap 4DVC S...

Page 16: ...e sealed around the vent pipes Use a non combustible seal off plate i e 22 gage sheet steel or unfaced fiberglass insulation 8 lb per square foot density minimum to seal around the vent pipes Whicheve...

Page 17: ...000 BTU Natural Gas Input To convert input from 40 000 BTU s to 33 000 BTU s Assuming the front door is already removed 1 Remove the log rack Use a 5 32 allen wrench by removing two screws on the fron...

Page 18: ...oundpanelsinfrontoftheholesonthesurroundbrackets Next insert two slotted 1 4 truss screws for each side surround panel and secure loosely 5 Fasten the top surround panel with the remaining two truss s...

Page 19: ...e Figure 15 The panel has keyhole slots where it mounts to the base Loosen the two nuts securing the panel using 3 8 wrench Carefully move out the panel far enough to access the back Do not pull the p...

Page 20: ...ak test solution retighten if necessary If the pressure is not sufficient make sure the gas supply line is large enough the supply regulator is properly adjusted and the total gas load for the residen...

Page 21: ...r will result in bigger flames and more color To adjust the air shutter insert a regular screwdriver into the slide adjustment and slide it side to side see Figures 19a and 19b CAUTION The air shutter...

Page 22: ...r 9 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier TO TURN OFF GAS TO APPLIANCE 1 Turn the burner ON OFF switch...

Page 23: ...e SIT Proflame Stepper Electronic Pilot Assembly Electronic Pilot Assembly Unit Mounted Controls Unit Mounted Controls Intermittent Standing Pilot Mode On Auto Pilot Mode Switch Thisappliancecanbeswit...

Page 24: ...s to indicate that it is ready to synchronize with the Remote transmitter Install 3 AAA type batteries in the Remote transmitter battery bay located on the base of the Remote With the batteries alread...

Page 25: ...d off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the high position see...

Page 26: ...r proper main burner operation at both high and low flame OPERATION RDV33 40 TCC Models Only No Blue Flame Center Soot at Flame Tip Dark Orange Flame IMPROPERLY BURNING FLAME Soot above Flame Tip No S...

Page 27: ...MOTE RECEIVER BLOWER SPEED CONTROL PILOT ON AUTO SWITCH AC DC ADAPTER POWER OUTLET BOX 6 WHT 5 BLUE WHT BLK WHT BLK BLK BLK 4 GRN GRN 8 GRN 3 GRAY 14 RED 9 GRN 2 RED 1 RED 3 BLK 2 BLK 1 RED PILOT ROOM...

Page 28: ...10 ORG 13 BLK 12 BRN 14 RED 4 PUR WHT BLK BLK WHT 4 GRN 8 GRN 2 BLK 3 BLK 1 RED 9 WHT 3 GRAY 2 RED GRN 1 2 3 4 1 Figure 28C Electronic Control Schematic Models RDV33 40 TCC NOTE SWITCH CONDITIONS GIVE...

Page 29: ...n those approved for use with this appliance o Check that the chimney and its outlet are open and free of soot block age or debris The venting system should be periodically examined by a qualified age...

Page 30: ...doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while reinstalling the glass door frame The glass door s o...

Page 31: ...Unplug the power supply cord from the electrical outlet prior to removing theblower Theblowercanbeaccessedthroughthebackwallofthefirebox Remove the insert face glass door log set and firebox liner pan...

Page 32: ...art No J7510 2 Place sight obstructers back over the threaded studs taking note that the upper and lower horizontal bar ends line up with grooves in sight obstructers see Detail A in Figure 33 3 Reins...

Page 33: ...llation on Pages 17 and 18 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed...

Page 34: ...with Manual Hi Lo Regulator 26 H8507 Cassette Assembly NG 40 000 BTU if LP also requires H8459 Conversion Kit For Models RDV TCC with Auto Hi Lo Regulator 27 H8490 3 8 NPT Pipe Nipple 8 28 H8498 Air S...

Page 35: ...STRATIONS ARE NOT TO SCALE REPLACEMENT PARTS RDV33 40 IPI RDV33 40 TCC 14 36 25 33 34 21 22 23 13 32 31 30 29 28 1 27 26 2 3 4 5 15 6 7 16 37 8 17 9 10 11 20 19 33 21 34 22 23 12 24 18 38 Facade Cast...

Page 36: ...ruction sheets included in kits Orifice Kits Main Burner 33 000 BTU converts from standard 40 000 BTU input to optional 33 000 BTU input Cat No Description H5924 Orifice Main Burner 36 Natural Gas 33...

Page 37: ...29 x 48 Black Trim Includes black trim x x x H8556 RDV DBV FP3341 D 33 x 41 Black Trim Includes black trim x x x H8557 RDV DBV FP3348 D 33 x 48 Black Trim Includes black trim x x x 75362 RDV DBV FP294...

Page 38: ...wing below Cat No Model Description 75156 RDV DBV PCFP3044 TOP Top Box 1 of 2 75157 RDV DBV PCFP3044 SIDES Sides Box 2 of 2 Pillar Cast Face Kits u Note 3 boxes to complete face 37 5 8 W x 23 3 4 H F2...

Page 39: ...1 8 49 36 51 UNIT FACTORY EQUIPPED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777...

Page 40: ...PED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUS...

Page 41: ...iance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Page 42: ...42 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTES...

Page 43: ...mage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions prov...

Page 44: ...s should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model numb...