IronStrike Ravenna RDV33 IPI Installation And Operation Manual Download Page 16

16

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

NOTE:

  The minimum vertical rise (exhaust vent) is 10 feet (3.1 M) and 

the maximum vertical rise is 35 feet (10.7 M). These dimensions are 

measured from the starting collars of the unit to the end of the vent pipe.

The fireplace and fireplace chimney must be clean and in good working 

order and constructed of non-combustible materials. Inspect chimney 

cleanouts for proper fit and seal.

Make sure that both liners will pass through existing damper area. 

Remove or lock damper to allow the passage of the flexible liners. If 

the damper will not allow the passage of both liners, DO NOT PROCEED 

FURTHER.  (If fireplace is masonry) Consult a local mason for removal 

of the damper without risk of structural damage or leakage (if the fire-

place is factory built) The appliance may NOT be installed into the fireplace.

        

WARNING

Direct-Vent Fireplace Insert Vent Requirements - Use liner 

listed to UL181 (Factory-made Air Ducts And Air Connec-

tors) or UL1777 (Chimney Liners) for the AIR INTAKE.  Use 

liner listed to UL1777 ONLY for the EXHAUST.

Do not substitute the heat-rated flex liner (UL1777) for 

the exhaust with any other type liner or a fire may result 

causing property damage, personal injury or loss of life.

Vertical Venting

The vent pipes must be connected to the proper collars on the unit and 

the exhaust vent pipe must be connected to the termination cap or the 

unit will not operate. 

The combustion air intake pipe can be connected to the termination cap 

(see 

Figure 7b

)

 or it can terminate inside the chimney 

(see 

Figure 7a

)

.  

If combustion air intake pipe is terminated inside the chimney and not 

connected to the actual termination cap the bottom opening of the chim-

ney (chimney throat) must be sealed around the vent pipes.  Use a non 

combustible seal-off plate (i.e. 22 gage sheet steel) or unfaced fiberglass 

insulation (8 lb per square foot density minimum) to seal around the vent 

pipes.  Whichever “seal off” method is used must effectively seal the area 

to prevent room air passage to the chimney of the fireplace.  The insulation 

may give off an odor during the first hour of operation.

Air Inlet Liner (for combustion air) When 

terminating the air inlet liner at this point, a 

positive flue connection is required (to ensure 

combustion air is drawn down the chimney 

only).

Exhaust 3" (75mm) UL 

1777. A full length liner 

is required from the 

exhaust outlet on appli-

ance to center collar of 

termination cap.

Positive Flue Con-

nection (sealing 

fireplace throat 

using a noncombus-

tible seal-off plate 

or insulation).

The outside air inlet does not 

require a full reline (if intake 

liner is terminated in chimney 

and a positive flue connection 

is achieved as specified).

Air Inlet

Exhaust

Air Inlet

Existing Fireplace Flue

(chimney)

Masonry and Factory Built Fireplaces

Figure 7a - Terminating Air Inlet in Chimney 

NOTE: Terminating the air intake liner as shown here may not be al-

lowed by some local codes.  Check with the authority having jurisdiction 

for your area.

Vertical Cap

Termination 

Connector

Exhaust

Intake

Combustion Air Intake

The existing fireplace chimneys 

may take various contours 

which the flexible liners will 

accommodate. However, keep 

the flexible liner as STRAIGHT 

as possible, avoid unnecessary 

bending.

Liner Requirements:

Vertical Height Min. = 10 ft. (3.1 M)

Vertical height Max. = 35 ft. (10.7 M)

Note: Measured from flue collar on 

unit to the end of the vent pipe or liner

Use 3" (76 mm) diameter listed gas 

vent liner (UL1777 ONLY) for the 

EXHAUST

Use 3" (76 mm) diameter listed 

liner (UL 181 or UL1777) for the 

AIR INTAKE.

The flexible vent pipe 

must NOT be allowed to 

sag behind  insert or in 

fireplace flue.

Figure 7b

Summary of Contents for Ravenna RDV33 IPI

Page 1: ...ly call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a...

Page 2: ...O CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact ac...

Page 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Page 4: ...t Leveling 14 Fan Control Module Switch RDV 33 40 TCC models only 15 Installation 15 21 Venting Installation 15 Zero Clearance Fireplace Installation 17 USING THIS MANUAL Please read and carefully fol...

Page 5: ...ls viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une ba...

Page 6: ...ing es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor de control en el panel de control del artefacto verifique que el interruptor opera el artefa...

Page 7: ...pareil Figure A Choisissezlalanguequiestprincipalementparl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour limi...

Page 8: ...se or anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the...

Page 9: ...ver use solid fuels such as wood paper cardboard coal or any flammable liquids etc in this appliance Plated surfaces must be cleaned with glass cleaner and a clean soft cloth before firing the first t...

Page 10: ...ural gas or propane Is NOT for use with solid fuels Is approved for sitting rooms and or bedrooms This appliance is suitable for installation into masonry or factory built fireplaces Fireplace Require...

Page 11: ...a nationally recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified to ANSI Z21 88 CS...

Page 12: ...rmation This appliance comes from the factory equipped to burn natural gas at a specified elevation Only IHP conversion kits can be used to convert from NG to LP or LP to NG Contact your IHP dealer fo...

Page 13: ...A 31 1 2 800mm Front Opening Width B 19 1 2 495mm Height C 18 457mm Rear Width D 16 406mm Fireplace Depth Top View Left Side View Right Side View Front View A B C D Figure 3 Minimum Fireplace Cavity...

Page 14: ...screws Repeat these steps for each adjusting leg Facing and Mantel Clearances Please note that the RDV33 IPI TCC mantel clearances are 4 less than the RDV40 IPI TCC mantel clearances as shown in Figu...

Page 15: ...tructions for installation and vent termination These appliances are approved for use with the following vent kits Amerivent Flex Liner 3 X 35 3AFL 35 Adaptor w Flashing 4DCAT33 Termination Cap 4DVC S...

Page 16: ...e sealed around the vent pipes Use a non combustible seal off plate i e 22 gage sheet steel or unfaced fiberglass insulation 8 lb per square foot density minimum to seal around the vent pipes Whicheve...

Page 17: ...000 BTU Natural Gas Input To convert input from 40 000 BTU s to 33 000 BTU s Assuming the front door is already removed 1 Remove the log rack Use a 5 32 allen wrench by removing two screws on the fron...

Page 18: ...oundpanelsinfrontoftheholesonthesurroundbrackets Next insert two slotted 1 4 truss screws for each side surround panel and secure loosely 5 Fasten the top surround panel with the remaining two truss s...

Page 19: ...e Figure 15 The panel has keyhole slots where it mounts to the base Loosen the two nuts securing the panel using 3 8 wrench Carefully move out the panel far enough to access the back Do not pull the p...

Page 20: ...ak test solution retighten if necessary If the pressure is not sufficient make sure the gas supply line is large enough the supply regulator is properly adjusted and the total gas load for the residen...

Page 21: ...r will result in bigger flames and more color To adjust the air shutter insert a regular screwdriver into the slide adjustment and slide it side to side see Figures 19a and 19b CAUTION The air shutter...

Page 22: ...r 9 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier TO TURN OFF GAS TO APPLIANCE 1 Turn the burner ON OFF switch...

Page 23: ...e SIT Proflame Stepper Electronic Pilot Assembly Electronic Pilot Assembly Unit Mounted Controls Unit Mounted Controls Intermittent Standing Pilot Mode On Auto Pilot Mode Switch Thisappliancecanbeswit...

Page 24: ...s to indicate that it is ready to synchronize with the Remote transmitter Install 3 AAA type batteries in the Remote transmitter battery bay located on the base of the Remote With the batteries alread...

Page 25: ...d off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the high position see...

Page 26: ...r proper main burner operation at both high and low flame OPERATION RDV33 40 TCC Models Only No Blue Flame Center Soot at Flame Tip Dark Orange Flame IMPROPERLY BURNING FLAME Soot above Flame Tip No S...

Page 27: ...MOTE RECEIVER BLOWER SPEED CONTROL PILOT ON AUTO SWITCH AC DC ADAPTER POWER OUTLET BOX 6 WHT 5 BLUE WHT BLK WHT BLK BLK BLK 4 GRN GRN 8 GRN 3 GRAY 14 RED 9 GRN 2 RED 1 RED 3 BLK 2 BLK 1 RED PILOT ROOM...

Page 28: ...10 ORG 13 BLK 12 BRN 14 RED 4 PUR WHT BLK BLK WHT 4 GRN 8 GRN 2 BLK 3 BLK 1 RED 9 WHT 3 GRAY 2 RED GRN 1 2 3 4 1 Figure 28C Electronic Control Schematic Models RDV33 40 TCC NOTE SWITCH CONDITIONS GIVE...

Page 29: ...n those approved for use with this appliance o Check that the chimney and its outlet are open and free of soot block age or debris The venting system should be periodically examined by a qualified age...

Page 30: ...doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while reinstalling the glass door frame The glass door s o...

Page 31: ...Unplug the power supply cord from the electrical outlet prior to removing theblower Theblowercanbeaccessedthroughthebackwallofthefirebox Remove the insert face glass door log set and firebox liner pan...

Page 32: ...art No J7510 2 Place sight obstructers back over the threaded studs taking note that the upper and lower horizontal bar ends line up with grooves in sight obstructers see Detail A in Figure 33 3 Reins...

Page 33: ...llation on Pages 17 and 18 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed...

Page 34: ...with Manual Hi Lo Regulator 26 H8507 Cassette Assembly NG 40 000 BTU if LP also requires H8459 Conversion Kit For Models RDV TCC with Auto Hi Lo Regulator 27 H8490 3 8 NPT Pipe Nipple 8 28 H8498 Air S...

Page 35: ...STRATIONS ARE NOT TO SCALE REPLACEMENT PARTS RDV33 40 IPI RDV33 40 TCC 14 36 25 33 34 21 22 23 13 32 31 30 29 28 1 27 26 2 3 4 5 15 6 7 16 37 8 17 9 10 11 20 19 33 21 34 22 23 12 24 18 38 Facade Cast...

Page 36: ...ruction sheets included in kits Orifice Kits Main Burner 33 000 BTU converts from standard 40 000 BTU input to optional 33 000 BTU input Cat No Description H5924 Orifice Main Burner 36 Natural Gas 33...

Page 37: ...29 x 48 Black Trim Includes black trim x x x H8556 RDV DBV FP3341 D 33 x 41 Black Trim Includes black trim x x x H8557 RDV DBV FP3348 D 33 x 48 Black Trim Includes black trim x x x 75362 RDV DBV FP294...

Page 38: ...wing below Cat No Model Description 75156 RDV DBV PCFP3044 TOP Top Box 1 of 2 75157 RDV DBV PCFP3044 SIDES Sides Box 2 of 2 Pillar Cast Face Kits u Note 3 boxes to complete face 37 5 8 W x 23 3 4 H F2...

Page 39: ...1 8 49 36 51 UNIT FACTORY EQUIPPED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777...

Page 40: ...PED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUS...

Page 41: ...iance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Page 42: ...42 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTES...

Page 43: ...mage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions prov...

Page 44: ...s should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model numb...

Reviews: