SPECIFICATIONS FOR MODEL 600 ULTRA FLAME ROD
ELECTRICAL
Primary Input Power
– 85 to 132 VAC, or 170 to 264 VAC, 50 or 60 Hz
Input Current, Monitoring only
– .07 A at 115VAC, .035 A at 230 VAC
Input Current, Ignition on
– .3 A at 115VAC, .15 A at 230 VAC
plus current to ignition transformer (5 AMPS MAX.)
Ignition Command Input
– 12 to 50 VDC or 85 to 264 VAC, 50 or 60 Hz
(using labeled DC and AC inputs)
Command Current
– .02 A DC at 50 VDC, .015 A RMS at 230 VAC
Maximum Capacitance Load
– 1.0 nF, flame rod drive to ground (through wire insulation)
OUTPUTS
Flame Relay
– DPDT contacts, rated 5A at 125 VAC, 277 VAC, and
30 VDC
Ignition Transformer Relay
– DPST contacts, rated 5A at 125 VAC and 250 VAC
Ignition Coil Drive
– A capacitance of 4.4 uF is discharged from 230 VDC
through the ignition coil tap at the AC line rate by a
4A, 400 V SCR
ENVIRONMENTAL
Ambient Temperature
– Controller 0°C to 60°C (32°F to 140°F)
SAFETY
Flame rod voltage
– 175 VAC at 115/230 VAC input
Flame rod current (not firing)
– Maximum current to ground <0.5ma
Rev: 0905