The Model 600 Ultra will operate equally well in sev-
eral configurations: flame rod only, flame rod with igni-
tion coil, and flame rod with ignition transformer. (It will
also operate with both an ignition coil and an ignition
transformer.)

The wiring for the flame rod only is shown in Figure 2;
it connects to the ROD/COIL pin on the controller.

If the ignition command is applied without the ignition
coil present, the voltage to the flame rod is not affected.
The pulsing of the ignition coil is done from the COIL
TAP pin of the controller.

The wiring of the ignition coil is shown in Figure 2. Pin
C for the coil is usually connected to ground in the igni-
tor assembly; this ground connection is not necessary
for coil operation. The flame rod operates through the
ignition coil when the ignition coil is not being pulsed.
When an ignition command is present, with every pulse
to the coil a strong spark is emitted from the coil tip
through the flame rod to ground. The pulse rate will be
the same as the line frequency, 50 or 60 pulses per
second. The air gap between the flame rod and ground
should be 2 to 3 mm. The nominal arc voltage is 7,000V.
If the gap is very large, there will be no arc when the
coil is pulsed.  Such pulsing will not be damaging to the
coil.  The peak voltage at the coil tip when no arc re-
sults will not exceed 11,000V.

When the ignition command is applied the AC power to
an ignition transformer is turned on by a DPST relay.
See Figure 2. The controller is normally shipped with
two .5 A fuses installed. If an ignition transformer is to be
used, the two 5 A fuses supplied in a small bag with the
controller must be installed in the controller.  Remove the
three black screws on each side of the controller, lift off
the top assembly, unplug the two .5 A fuses, plug in the
two 5 A fuses, and reassemble the controller.

FRONT PANEL FUNCTIONS AND SETUP

Six numeric LED digits arranged vertically provide a
graphic visual display of the flame signal.  If the Flame
Rod is connected and the AC power is on (green
POWER LED will be on) and there is no flame signal,
none of the numeric digits will be on.  With a weak
flame signal, either the “1” or “2” digits will be on but
the Flame Relay will be off. A stronger signal will be
indicated by “3” or a higher digit turning on; with this
stronger signal the Flame Relay will be turned on.

In normal operation when the flame is present the “5”
or “6” digits should be on with, perhaps, digit “4” turn-
ing on occasionally.

If the “3” or “4” digits are on most of the time, the gain
should be increased by moving P2 to a higher gain posi-
tion. If the “6” digit is on steadily, the gain is probably
set too high; move the P2 plug to a lower gain position.

If the LED for ROD FOULED is on, the Model 600
controller will continue to operate, but this is a warning
that a small amount of AC current is flowing from the
flame rod to ground.  This means that the flame rod or
its mount probably needs cleaning.

If the fouling gets to be significant, approaching the point
where the flame signal could be affected, the LED for
ROD FAULT will turn on, causing the flame relay to
open. This fault condition will be removed as soon as
the fouling is sufficiently reduced.

CONTACT INFORMATION

For further information contact:

Sales and Applications:

IRIS SYSTEMS INC.
7583 Vantage Place
Delta, BC, Canada V4G 1A5

Ph. 800-667-IRIS,  FAX 604-581-9790

email: [email protected]

Manufacturing and Service:

IRIS SYSTEMS INC. (JB Systems, Inc.)
4944 - 113th Avenue North
Clearwater, FL 33760

Ph. 727-545-3900,  FAX 727-547-9589

Summary of Contents for 600 Ultra

Page 1: ...FLAME MONITORING SYSTEM WORLD LEADER IN FLAME MONITORING MODEL 600 ULTRA FLAME ROD APPLICATION MANUAL ...

Page 2: ...vided The flame rod itself can be shorted to ground indefinitely without harm to the unit If the flame rod becomes fouled so that an unreasonably large amount ofAC current flows from the flame to ground first a yellow ROD FOULED LED is turned on If the AC current in creases further a ROD FAULT LED is turned on and the flame relay is opened Note that the Model 600 Ultra controller distinguishes bet...

Page 3: ...ntroller Remove the three black screws on each side of the controller lift off the top assembly unplug the two 5 A fuses plug in the two 5 A fuses and reassemble the controller FRONT PANELFUNCTIONSAND SETUP Six numeric LED digits arranged vertically provide a graphic visual display of the flame signal If the Flame Rod is connected and the AC power is on green POWER LED will be on and there is no f...

Page 4: ... ROD GOOD SIG A ROD ROD FOULED GAIN 1 GAIN 2 NO JMPR MAX GAIN 4 SIGNAL Relay On WEAK SIGNAL Relay On POOR SIGNAL Relay Off MODEL 600 ULTRA GND 115 VAC 50 60 HZ 230 VAC 50 60 HZ SIG B ROD XFMRXFMR AC IGN COM IGN DC IGN RF A RF A RF A RF B GAIN 3 RF B RF B TURN IGN ON TO XFMR LINE INPUT SELECT FOR LINE INPUT P1 P2 P3 P4 P5 ...

Page 5: ...D XFMRXFMR AC IGN COM IGN DC IGN RF A RF A RF A RF B GAIN 3 RF B RF B TURN IGN ON TO XFMR LINE INPUT SELECT FOR LINE INPUT ROD FLAME ROD IGNITION FLAME IGNITION COIL GAIN 1 GAIN 2 NO JMPR MAX GAIN 4 GAIN 3 5A OR 5A 5A OR 5A FLAME ROD ONLY AC IN GND TO IGN XFMR TAP COIL COIL ROD P1 P2 P3 P4 P5 GND C B A COIL TIP GND GND 230 VAC POSITION 115 VAC POSITION FIGURE 2 WIRING FOR MODEL 600 FLAME ROD ULTRA...

Page 6: ...rent 02 A DC at 50 VDC 015 A RMS at 230 VAC MaximumCapacitanceLoad 1 0nF flame rod drive to ground through wire insulation OUTPUTS FlameRelay DPDT contacts rated 5Aat 125 VAC 277 VAC and 30 VDC IgnitionTransformerRelay DPST contacts rated 5Aat 125 VAC and 250 VAC IgnitionCoilDrive Acapacitance of 4 4 uF is discharged from 230 VDC through the ignition coil tap at theAC line rate by a 4A 400 V SCR E...

Reviews: