Tumblers – T30 and T45

18

4-08-43

Electrical Requirements for Gas and 
Steam Models

Refer to 

Table 4

 and 

Table 5

.

NOTE: Minimum wire sizes are obtained from 

Canadian Electrical Code for 75°C Conductors 

and are intended for use as a guideline only. 

Electrical connections should be made only by a 

qualified electrical contractor in accordance with 

all applicable local and national requirements.

For T30 Gas and Steam Models 

(For Total Machine):

NOTE: Electrical specifications below are subject 

to change without notice. Always refer to product 

serial plate for most current specifications of 

product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only – Each tumbler must be 

connected to its own individual branch circuit 

breaker, not fuses, to avoid the possibility of “single 

phasing” and causing premature failure of the 

motor(s).

Table 4 

Serial Plate Voltage

Terminal Block

Connections 

Required

Current 

(Amps)

Recommended 

Fuse or 

Breaker Rating 

(Amps)

Breaker 

Poles

Recommended 

Minimum

Conductor Size

(AWG [mm

2

])

120V/60 Hz/1ph

L1, Neutral, 

and ground

16.0

20

1

12 (3.31)

208-240V/60Hz/1ph

L1, L2, Neutral, 

and ground

8.0

10

2

14 (2.08)

100V/60Hz/1ph

L1, Neutral, 

and ground

22.0

30

1

10 (5.26)

200-220V/60Hz/1ph

L1, Neutral, 

and ground

11.6

15

1

14 (2.08)

100V/50Hz/1ph

L1, Neutral, 

and ground

24.2

35

1

8 (8.37)

200V/50Hz/1ph

L1, Neutral, 

and ground

15.0

20

1

12 (3.31)

230-240V/50Hz/1ph

L1, Neutral, 

and ground

15.0

20

1

12 (3.31)

200-208V/60Hz/3ph

L1, L2, L3, 

and ground

6.4

10*

3

14 (2.08)

240V/60Hz/3ph

L1, L2, L3, 

and ground

6.4

10*

3

14 (2.08)

200V/50Hz/3ph

L1, L2, L3, 

and ground

5.8

10*

3

14 (2.08)

230-240V/50Hz/3ph

L1, L2, L3, 

and ground

7.0

10*

3

14 (2.08)

380V/50 or 60Hz/3ph

L1, L2, L3, 

and ground

3.0

10*

3

14 (2.08)

400-415V/50Hz/3ph

L1, L2, L3, 

and ground

3.2

10*

3

14 (2.08)

460-480V/60Hz/3ph

L1, L2, L3,

and ground

3.3

10*

3

14 (2.08)

* 3 Phase machines should not have fuses, breakers only.

Summary of Contents for IPD30STE2-ITT30E

Page 1: ...ll instructions T30 and T45 Tumblers START 25C HIGH TEMP MED TEMP LOW TEMP NO HEAT 1 2 3 SELECT TEMP INSERT COIN PUSH START 1 2 3 SELECT TEMP INSERT COIN PUSH START START 25C HIGH TEMP MED TEMP LOW TEMP NO HEAT T477C T477C On Premise Laundry Planning Handbook ...

Page 2: ...Table of Contents Tumblers T30 and T45 2 Introduction 2 Model Identification 2 Specifications and Dimensions 4 Cabinet Dimensions 5 Exhaust Outlet Locations 6 Gas Connection Locations 7 Electrical Connection Locations 8 Steam Connection Locations 9 Installation 10 Pre Installation Inspection 10 Exhaust Requirements 12 Layout 12 Make Up Air 12 Venting 12 Individual Venting 13 Manifold Venting 14 El...

Page 3: ...P NO HEAT 1 2 3 SELECT TEMP INSERT COIN PUSH START 1 2 3 SELECT TEMP INSERT COIN PUSH START START 25C HIGH TEMP MED TEMP LOW TEMP NO HEAT T477C Gas Steam Electric T30 IPD30STG2 ITT30L IPD30STG2 ITT30N IPD30STS2 ITT30S IPD30STE2 ITT30E T45 IPD45STG2 ITT45L IPD45STG2 ITT45N Not Applicable Not Applicable 3O DX4 OPL EO LED OPL SD single drop 3V DX4 vended QT dual digital timer SX single drop prep for ...

Page 4: ... Multiply By To Obtain Btu 0 252 kCal Pounds sq inch 0 06895 Bars Btu 1055 Joules Pounds sq inch 0 070 kg sq cm Inch 25 4 Millimeters Pounds lbs 0 454 Kilograms Inches W C 0 036 Pounds sq inch Boiler Horsepower 33 479 Btu hr Inches W C 0 249 kPa Boiler Horsepower 34 5 lbs steam hr lb inch2 psi 6 895 kPa CFM 0 471 liters second ft3 28 32 Liters kW 3414 Btu hr ...

Page 5: ...eight Pounds kg 2 x 30 2 x 13 6 2 x 45 2 x 20 5 Drive Motor Horsepower 1 4 1 2 Fan Motor Horsepower 1 4 1 2 Maximum Airflow per Pocket C F M l sec 50 Hertz 340 160 N A 60 Hertz 400 189 600 283 Maximum Static Back Pressure Inches W C mbar 50 Hertz 0 8 2 0 N A 60 Hertz 0 9 2 3 0 9 2 3 Gas Models Gas Connection 1 2 in NPT 1 2 in NPT Gas Burner Rating Btu hr kW Mj hr 73 000 21 4 77 95 000 27 8 100 2 E...

Page 6: ...32N TMB2332N C E F H J B D G I A Models A B C D E T30 28 in 711 mm 49 in 1245 mm 48 25 in 1226 mm 11 4 in 290 mm 10 7 in 272 mm T45 31 88 in 810 mm 50 4 in 1280 mm 49 3 in 1252 mm 10 3 in 262 mm 9 3 in 236 mm Models F G H I J T30 25 02 in 636 mm 42 76 in 1086 mm 27 38 in 695 mm 31 5 in 800 mm 76 25 in 1937 mm T45 29 37 in 746 mm 48 62 in 1235 mm 30 50 in 775 mm 34 5 in 876 mm 81 25 in 2063 75 mm ...

Page 7: ...ers T30 and T45 6 4 08 43 Exhaust Outlet Locations TMB1969N TMB1969N B C A Models Rear Exhaust Diameter A B C T30 Elliptical Fits 8 in 203 mm 36 54 in 928 mm 4 25 in 108 mm 62 42 in 1585 mm T45 Elliptical Fits 10 in 254 mm 40 88 in 1038 mm 4 75 in 121 mm 66 00 in 1676 mm ...

Page 8: ... 43 7 Gas Connection Locations TMB1970N 1 1 2 in NPT TMB1970N A B C 1 Models Gas Connection A B C T30 Non CE and Non Australian 75 20 in 1910 mm 1 74 in 44 mm 36 84 in 936 mm CE and Australian 75 28 in 1912 mm 2 5 in 64 mm 30 60 in 777 mm T45 78 75 in 2000 mm 4 12 in 105 mm 42 88 in 1089 mm ...

Page 9: ...Electrical Connection Locations TMB1971N TMB1971N A B E D C GAS AND STEAM ELECTRIC Models Electric Service Gas and Steam Models Electric Models A B C D E T30 59 in 1498 mm 1 75 in 44 mm 35 63 in 905 mm 73 21 in 1859 mm 2 28 in 58 mm T45 62 5 in 1588 mm 1 75 in 44 mm N A N A N A N A Not Applicable ...

Page 10: ...nd T45 4 08 43 9 Steam Connection Locations NOTE All connections use 3 4 inch NPT pipe TMB1972N C D A B A B Models Inlet Outlet A C B D T30 Upper 73 93 in 1877 mm 6 29 in 160 mm 62 71 in 1592 mm 2 39 in 61 mm T30 Lower 36 35 in 923 mm 6 29 in 160 mm 25 13 in 638 mm 2 39 in 61 mm ...

Page 11: ...possible and check the items listed on the packing list Advise the carrier of any damaged or missing articles as soon as possible A written claim should be filed with the carrier immediately if articles are damaged or missing IMPORTANT Warranty is void unless tumbler is installed according to instructions in this manual Installation should comply with minimum specifications and requirements detail...

Page 12: ...rance allowed for trim 3 4 in 102 mm Maximum Header Thickness 4 12 in 305 mm Minimum Clearance 5 24 in 610 mm Minimum 36 in 914 mm recommended for maintenance purposes 6 Provision for Make Up Air Minimum 1 5 square feet T30 models minimum 2 square feet T45 models Location for reference only May be anywhere behind tumbler 7 0 25 in 6 mm recommended for removal or installation purposes zero clearanc...

Page 13: ...y the shortest possible route Proper sized exhaust ducts are essential for proper operation All elbows should be sweep type Exhaust ducts must be assembled so the interior surfaces are smooth so the joints do not permit the accumulation of lint DO NOT use plastic or thin foil ducts rigid metal ducts are recommended Use exhaust ducts made of sheet metal or other noncombustible material DO NOT use s...

Page 14: ...nt length of a duct required for an installation exceeds the maximum allowable equivalent length the diameter of a round duct must be increased by 10 for each additional 20 feet 6 1 m Cross section area of a rectangular duct must be increased by 20 for each additional 20 feet 6 1 m Refer to Table 1 to determine equivalent venting NOTE The maximum length of a flexible metal duct must not exceed 2 4...

Page 15: ...inimum diameters and should be increased if the collector length exceeds 14 feet 4 3 m and two 90 elbows The diameter of a round duct must be increased by 10 for each additional 20 feet 6 1 m Cross sectional area of a rectangular or square duct must be increased 20 for each additional 20 feet 6 1 m Refer to Table 2 or Table 3 to determine equivalent ducting sizing The collector duct may be rectang...

Page 16: ...ector operating NOTE Never connect a tumbler duct at a 90 angle to the collector duct Refer to Figure 3 Doing so will cause excessive back pressure resulting in poor performance Never connect two tumbler exhaust ducts directly across from each other at the point of entry to the collector duct With the tumbler in operation and both pockets running airflow at any point in the duct should be at least...

Page 17: ...pical L K J I H G F E D C B A 3 1 2 ONE MANIFOLD ASSEMBLY Duct Station T30 T45 8 in 203 mm Duct 10 in 254 mm Duct A 8 in 203 mm 10 in 254 mm B 12 in 305 mm 15 in 381 mm C 15 in 381 mm 18 in 457 mm D 17 in 432 mm 21 in 533 mm E 19 in 483 mm 24 in 610 mm F 21 in 533 mm 26 in 660 mm G 23 in 584 mm 28 in 711 mm H 24 in 610 mm 30 in 762 mm I 26 in 660 mm 32 in 813 mm J 27 in 686 mm 33 in 838 mm K 28 in...

Page 18: ...J I L K J I CONTINUE TO A CONTINUE TO A TWO MANIFOLD ASSEMBLIES Duct Station T30 T45 8 in 203 mm Duct 10 in 254 mm Duct A 12 in 305 mm 15 in 381 mm B 17 in 432 mm 22 in 559 mm C 22 in 559 mm 26 in 660 mm D 25 in 635 mm 30 in 762 mm E 27 in 686 mm 34 in 864 mm F 30 in 762 mm 37 in 940 mm G 33 in 838 mm 40 in 1016 mm H 34 in 864 mm 43 in 1092 mm I 37 in 940 mm 46 in 1168 mm J 39 in 991 mm 47 in 1194...

Page 19: ...ng and causing premature failure of the motor s Table 4 Serial Plate Voltage Terminal Block Connections Required Current Amps Recommended Fuse or Breaker Rating Amps Breaker Poles Recommended Minimum Conductor Size AWG mm2 120V 60 Hz 1ph L1 Neutral and ground 16 0 20 1 12 3 31 208 240V 60Hz 1ph L1 L2 Neutral and ground 8 0 10 2 14 2 08 100V 60Hz 1ph L1 Neutral and ground 22 0 30 1 10 5 26 200 220V...

Page 20: ...rrent Amps Recommended Fuse or Breaker Rating Amps Breaker Poles Recommended Minimum Conductor Size AWG mm2 208 240V 60Hz 1ph L1 L2 Neutral and ground 12 0 15 2 14 2 08 200 208V 60Hz 3ph L1 L2 L3 and ground 9 6 15 3 14 2 08 240V 60Hz 3ph L1 L2 L3 and ground 9 6 15 3 14 2 08 200V 50Hz 1ph L1 Neutral and ground 11 2 15 1 14 2 08 230 240V 50Hz 1ph L1 Neutral and ground 10 8 15 1 14 2 08 Table 5 ...

Page 21: ... connected to its own individual branch circuit breaker not fuses to avoid the possibility of single phasing and causing premature failure of the motor s For 21 kW T30 Electric Models Table 6 Serial Plate Voltage Terminal Block Connections Required Current Amps Recommended Breaker Rating Amps Breaker Poles Recommended Minimum Conductor Size AWG mm2 200 208V 60Hz 3ph L1 L2 L3 and ground 62 80 3 4 2...

Reviews: