            RACK TOWER ONLINE UPS

 

 

 

                                                                                             

      

 

                4.011.2017 

 

 

 

 

 

                                            RTS-ON-user-manual_ENG-R1 

 

16 

 Exit from the setting interface. Press and hold function setting key

for more than half a second (less than 2 

seconds), exit from the setting interface and return to main interface. 

2 5 %

5 0 %

7 5 %

1 0 0 %

2 5 %

5 0 %

7 5 %

1 0 0 %

ST

DB

Y

   

2 5 %

5 0 %

7 5 %

1 0 0 %

2 5 %

5 0 %

7 5 %

1 0 0 %

ST

DB

Y

 

4.6.4 Low voltage of battery setting 

 Enter the setting interface. Press and hold the function setting key

for more than 2 seconds, then come 

to setting interface, Press and hold the inquiring key (

,

for more than half a second(less than 2 

s

econds), select the function setting, choose battery voltage setting interface, at the moment, the letters “bat” will 

flash. 

 Enter the battery voltage selecting interface. Press and hold the function setting key

for more than half a 

second(less than 2 seconds), then come to setting interface of battery voltage, this time, the numerical value will 

flash. Press and hold the inquiring key (

,

)

 for more than half a second (less than 2 seconds), select the 

numerical value in accordance with “battery” function. The provided voltages are 10V, 10.2V, 10.5V, numbers 

stand for the voltage of each battery, you can choose anyone by yourself (The default is 10V), anyone has been 

chosen, under BAT mode, UPS will shutdown when its battery voltage achieve the voltage you chose.  

 Confirm the battery voltage selecting interface. After selecting numerical value, press and hold the function 

setting

, for more than half a second (less than 2 seconds). Now, the battery setting function is completed 

and the numerical value will light without flash. 

 Exit from the setting interface. Press and hold function setting key

for more than half a second (less than 2 

seconds), exit from the setting interface and return to main interface. 

Summary of Contents for RTS-ON-10k0-3U-LCD-BC192

Page 1: ...NUAL Thanks for using our products Please strictly obey all the instructions in this manual and pay attention to all the warning and operation information It is not advisable to install or operate the machine before reading this manual ...

Page 2: ...uestions please contact local service center or dealer 1 2 Battery safety instructions Battery life cycle will be shortened as environment temperature rise Replacing battery periodically can help to keep UPS in normal state and assure backup time required Battery replacement should be done by authorized technician If you want to replace the battery cable please purchase it from our local service c...

Page 3: ...ether this UPS is the model you want to buy Check the model name showed both on the front panel and rear panel of UPS to confirm Model Type RTS ON 1k0 2U LCD 2x9 1KVA RT Standard model RTS ON 2k0 2U LCD 4x9 2KVA RT Standard model RTS ON 3k0 2U LCD 6x9 3KVA RT Standard model RTS ON 6k0 6U LCD 16x7 6KVA RT Standard model RTS ON 10k0 6U LCD 16x9 10KVA RT Standard model RTS ON 1k0 2U LCD BC24 1KVA RT ...

Page 4: ...PF 1KVA RT rear panel b 0 9PF 1 5K 2KVA RT rear panel EPO USB RS232 TEL MODEM FAX IN OUT INTELLIGENT SLOT 5 7 8 9 11 2 4 6 10 3 INPUT FUSE 125VAC 25A RESET 48VDC 40A EXT BATTERY OUTPUT SOCKET OUTPUT N L RESET R E S E T T O 1 20A 15A DC OUTPUT DC OUTPUT 72VDC 72VDC 9 9 c 0 9PF 3KVA RT rear panel d 0 9PF Battery Pack rear panel 2 2 2 The type of 220V output could be 208V 210V 220V 230V 240V A Standa...

Page 5: ...MODEM FAX IN OUT 9 10 2 1 8 4 5 7 6 a 0 9PF 1KVA RT rear panel b 0 9PF 1 5K 2KVA RT rear panel RESET FUSE 250VAC 20A INPUT 72VDC 40A EXT BATTERY OUTPUT SOCKET EPO USB TEL MODEM FAX IN OUT INTELLIGENT SLOT RESET R E S E T T O RS232 2 1 4 6 9 10 8 5 7 3 OUTPUT L N INPUT L N ON OFF RS232 USB EPO RS232 2 3 9 7 4 5 6 8 11 12 c 0 9PF 3KVA RT rear panel d 0 9PF 6 10KVA RT rear panel Input Power Terminals...

Page 6: ...nnect the UPS with the socket which rated current is less than the Maximum input current of the UPS All the power socket should be configured with earthing device for safety UPS could be electrified or powered no matter the input power cable is tied or not even when the UPS is off The only way to cut off the output is switching off the UPS and disconnecting the mains power supply For all standard ...

Page 7: ... in step2 and step3 Make sure the mains power is off when you move it The battery pack and the UPS unit can be put together install as the following steps please do not install the UPS upside down The UPS unit and the battery pack also can be placed horizontally without support feet remember that put the battery pack under the UPS unit The battery pack is heavy be careful when you move it 3 2 2 Ra...

Page 8: ...e malfunctioning at the same time and the parallel UPS system is still steady The larger X is the system is more reliable N X is the best method for high reliability Just install a little more simple accessories at most 8 UPS could work together to form a flexible parallel system This structure of power supply system increases the power safety and reliability For example two single UPS make up a p...

Page 9: ... the parallel system there is only one way to wire two UPS use two parallel wires to connect two UPS like the diagram showing below connection looks like a circle If three or more than three UPS are needed the connection is similar you can refer to the diagram as below How many UPS unit how many parallel wires you need OUTPUT L N INPUT L N OUTPUT L N INPUT L N OUTPUT L N INPUT L N OUTPUT L N INPUT...

Page 10: ...les of all UPS together to a common terminal block Connect input cables of all UPS together to one common utility power terminal block I nput com m on term i nal bl ock U ti l i ty pow er suppl y O utput com m on term i nal bl ock Load Load Load Parallel UPS system view Short Pin ...

Page 11: ...on of single UPS Before starting the system need to set up different ID for each UPS specific settings please refer to the instruction of ID setting which is given in single UPS panel function setting Turn on the parallel system Start the system with mains power After inputting the mains power turn on any one UPS of system others will start by themselves at same time All UPS will enter into Line m...

Page 12: ... are instructed to configure different battery voltage as below sheet More or less units are forbidden or else something abnormal or faulty will appear Type Battery Quantity unit Battery Voltage volt 1KVA 2 3 24 36 1 5KVA 4 48 2KVA 4 6 48 72 3KVA 6 8 72 96 6KVA 16 192 10KVA 16 192 One end of battery cable is for UPS terminals while the other end with triple cables is for battery terminals Correct ...

Page 13: ...anel of UPS it s green in some emergent cases users could cut off the output of UPS immediately by operating EPO port Wiring diagram as below Normally pin1 and pin2 are connected so that the machine can be working normally When some emergencies happen and when users do have to cut off the output just need to disconnect the connection between pin1 and pin2 or there is a anther useful simple way is ...

Page 14: ...card option Insert the dry contact card into the intelligent slot it s another type function of intelligent monitoring Foot Definition PIN1 ON UPS is malfunctioning PIN2 ON Alarm system failure PIN3 Ground PIN4 Remote shutdown PIN5 Common PIN6 ON Bypass mode PIN7 ON Battery low PIN8 ON Inverter mode OFF Bypass mode PIN9 ON No AC power in USB card option USB card is designed specially for high freq...

Page 15: ...mode or CUCF mode UPS runs the self test function Press and hold the key for more than 1 second in battery mode UPS runs the mute function ROTATE key Press and hold and for more than 5 second Change the direction to display items ROTATE TEST MUTE VAC HZ OUTPUT 25 50 75 100 25 50 75 100 L I N E ON OFF 2 5 5 0 7 5 1 0 0 2 5 5 0 7 5 1 0 0 OUTPUT L I N E VAC HZ ROTATE TEST MUTE ON OFF After finishing ...

Page 16: ...and hold the key for more than half a second less than 2 seconds Select the set option FUNCTION SETTING key Non function setting mode Press and hold the key for more than 2 seconds Function setting interface Function setting mode Press and hold the key for more than half a second less than 2 seconds Enter the function setting option Press and hold the key for more than 2 seconds exit from this fun...

Page 17: ...load and battery capacity indication each grid of which represents 25 B The fan icon is for fan working indication when fan normally runs the icon will display rotation if the fan is not connected or faulty the icon blinks C Press the mute button under the battery mode buzzer icon will blink it will disappear in other cases D Fault icon will be on when UPS is in fault mode otherwise it will not Di...

Page 18: ...disconnected press and hold the ON key for more than half a second to start UPS The operation of UPS in the process of start is almost the same as that when mains power is on After the self test finishes the corresponding LED lights and UPS are working in battery mode 4 4 2 Turn off operation Turn off the UPS in line mode Press and hold the OFF key for more than half a second to turn off the UPS a...

Page 19: ...responding word is ON if not the word is OFF It can be determined by yourself Confirm the ECO selecting interface After selecting ON or OFF press and hold the function setting key for more than half a second less than 2 seconds Now the ECO setting function is completed and the ON or OFF will light without flash Exit from the setting interface Press and hold function setting key for more than 2 sec...

Page 20: ... Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interface press and hold the inquiring key for more than half a second less than 2 seconds select the function setting choose output voltage setting interface at the moment the letters OPU will flash Enter the output voltage setting interface Press and hold the function setting key for...

Page 21: ...han half a second less than 2 seconds then come to setting interface of battery voltage this time the numerical value will flash Press and hold the inquiring key for more than half a second less than 2 seconds select the numerical value in accordance with battery function The provided voltages are 10V 10 2V 10 5V numbers stand for the voltage of each battery you can choose anyone by yourself The d...

Page 22: ...econds then come to setting interface of CF at this time the letters CF will not flash any more The ON or OFF will flash Press and hold the inquiring key for more than half a second less than 2 seconds to determine whether the CF function is used or not If used the corresponding word is ON if not the word is OFF It can be determined by yourself Confirm the CF selecting interface After selecting ON...

Page 23: ...ction setting key for more than half a second less than 2 seconds then come to setting interface of OPF at this time the letters OPF will not flash any more The OFF or 50HZ 60HZ will flash Press and hold the inquiring key for more than half a second less than 2 seconds to determine whether the CF function is used or not If used select 50HZ or 60HZ according to you It is determined by yourself the ...

Page 24: ...e letters Id will not flash any more The numerical value next to the Id will flash Press and hold the inquiring key for more than half a second less than 2 seconds select the numerical value The provided ID numbers are 1 2 3 4 5 6 7 8 you can choose anyone by yourself The default value is 1 Confirm the output voltage setting interface After selecting numerical value press and hold the function set...

Page 25: ...ge is 120V 220V the output frequency is 50Hz VAC HZ OUTPUT 25 50 75 100 25 50 75 100 L I N E VAC HZ OUTPUT 25 50 75 100 25 50 75 100 L I N E Load Display the numerical value of the active power WATT and apparent power VA of the load For example as the following graphics shows the WATT of the load is 800W 900W VA is 1000VA when disconnect load it is a normal phenomenon to show a small numerical val...

Page 26: ...he following picture shows the battery voltage is 24V 36V the capacity of battery is 100 the capacity of battery is approximately reckoned according to the battery voltage 25 50 75 100 25 50 75 100 VDC L I N E B A T T E R Y 25 50 75 100 25 50 75 100 VDC L I N E B A T T E R Y Press and hold the inquiring key for more than 2 seconds LCD begins to display the items circularly and orderly which transf...

Page 27: ...ttery mode LED indications on front panel in battery mode are as following both the inverter green LED and battery yellow LED is on the buzzer beeps once every 4 seconds The warning red LED will be on while beeping When the mains power is low or unstable UPS will turn to battery mode at once 4 4 ECO mode LED indications on front panel in ECO mode are as following both the inverter green LED and by...

Page 28: ...warning code list of the LED light and display panel Appendix 1 The table of the fault code Fault code Fault type Bypass output Note 0 1 2 3 4 Bus high yes 5 6 7 8 9 Bus low yes 10 11 12 13 14 Bus unbalance yes 15 16 17 18 19 Bus soft start fail yes 20 21 22 23 24 Inverter soft start fail yes 25 26 27 28 29 Inverter high yes 30 31 32 33 34 Inverter low yes 35 36 37 38 39 Bus discharge fail yes 40 ...

Page 29: ...Inverter mode mains power Mains power voltage N Mains power high low voltage protection switch to battery mode One beep 4 sec 2 Battery mode Battery voltage normal One beep 4 sec Warning for abnormal voltage of battery One beep sec 3 Bypass mode Mains power normal under Bypass One beep 2 mins Mains power high voltage warning under Bypass One beep 4 sec Mains power low voltage warning under Bypass ...

Page 30: ... 8 Faults mode Long beep LED indicator lights long time LED indicator flicker LED indicator status depends on other conditions Note End user need to provide below information when require to maintain the UPS UPS Model No Serial No Date of fault occurrence Fault detail LED status noise AC power situation load capacity for long back up type battery capacity configuration is also necessary 6 Trouble ...

Page 31: ...rt circuit Turn of the UPS and disconnect all the load make sure there no any fault or internal short circuit of the load And then restart the UPS if failure still please contact the supplier Fault LED on audible buzzer persistently alarm the fault code is 50 54 Over load Please check the load level and disconnect the noncritical devices recount the total capacity of your load and reduce the load ...

Page 32: ...y descend Please change new battery contact your supplier to get the new battery and spare parts UPS doesn t have any power go through even main power on UPS input breaker disconnects Please reset the circuit breaker by manual Attention When the output is short circuited the action of the protection of the UPS will show up Before turning off the UPS please make sure to disconnect the entire load a...

Page 33: ...t voltage range the type of 220V 115 295 5VAC half load 145 295 5VAC full load Input voltage range the type of 120V 55 145 5VAC 60 LOAD 65 145 5VAC 70 LOAD 75 145 5VAC 80 LOAD 85 145 5VAC 100 LOAD Input frequency range 45 55Hz 0 5 50Hz type 55 65Hz 0 5 60Hz type Input current 220V 8A max 12A max 15A max 23A max 120V 14A max 21A max 27A max 40A max PFC 0 98 THDI 6 Bypass voltage range 220V Rated ou...

Page 34: ...battery mode 50 60 0 2 Hz Phase locked rate 1Hz s Total voltage harmonic distortion Full linear load 3 Full nonlinear load 5 Battery Battery type Sealed lead acid maintenance free battery Quantity 2 3 4 4 6 6 8 DC voltage 24V 36V 48V 48V 72V 72V 96V Inbuilt battery 9AH 12V 7AH 12V 9AH 12V 9AH 12V 7AH 12V 9AH 12V 7AH 12V Output voltage 27 1 0 4V 40 6 0 5V 54 2 0 6V 54 2 0 6V 81 3 0 9V 81 3 0 9V 108...

Page 35: ... current 46A max 76A max PFC 0 99 THDI 5 Bypass voltage range 160V Rated output voltage 32V Output Output voltage 208VAC 220VAC 230VAC 240VAC Setting available via LCD Output PF 0 9 Output power Watt 5400 9000 Inverter overload capability 105 125 3 mins 125 150 30 secs 150 100ms Voltage accuracy 1 Load crest 3 1 From AC mode to BAT mode 0ms transfer time From BAT mode to AC mode 0ms transfer time ...

Page 36: ...on Output short circuit protection Communication port RS232 SNMP card USB Dry contact Software function Graphics analyze Switch on off UPS system Monitor UPS working status History record and event log Display LCD LED Derate capacity to 70 in CUCF mode and to 90 when the output voltage is adjusted to 208VAC Appendix 5 Physical The type of 220V Rated Capacity 1KVA 1 5KVA 2KVA 3KVA Dimension W D H U...

Page 37: ...ack 52 52 Appendix 6 Physical The type of 120V Rated Capacity 1KVA 1 5KVA 2KVA 3KVA Dimension W D H Long 440 468 88 Standard 440 468 88 With Internal battery 440 468 88 Without Internal battery 440 690 88 With Internal battery Battery pack 440 468 88 Weight Kg Long 6 12 12 13 Standard WOIB 12 12 13 WIB 12 28 5 28 5 33 5 Battery pack 17 17 23 WOIB Without Internal battery WIB With Internal battery ...