RACK TOWER ONLINE UPS
4.011.2017
RTS-ON-user-manual_ENG-R1
14
4.6 Single UPS panel function setting
UPS has setting function. It can run the setting in any mode. After setting, it will become effective at once when
meets some standards. The set information can be saved only when the battery connected and normally turning off
the UPS.
4.6.1 ECO mode setting
①
Enter the setting interface. Press and hold the function setting key
for more than 2 seconds, then come to
setting interface, the letters “ECO” will flash;
②
Enter the ECO setting interface. Press and hold the function setting key
for more than half a second(less
than 2 seconds), then come to setting interface of ECO, at this time, the letters “ECO” will not flash any more.
The “ON” (or OFF) will flash. Press and hold the inquiring key (
,
)
for more than half a second (less than
2 seconds) to determine w
hether the ECO function is used or not. If used, the corresponding word is “ON”, if not,
the word is “OFF”. It can be determined by yourself.
③
Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function setting key
for
more than half a second (less than 2 seconds). Now, the ECO setting function is completed and the “ON” or
“OFF” will light without flash.
④
Exit from the setting interface. Press and hold function setting key
for more than 2 seconds, exit from the
setting interface and return to main interface.
2 5 %
5 0 %
7 5 %
1 0 0 %
2 5 %
5 0 %
7 5 %
1 0 0 %
ST
DB
Y
2 5 %
5 0 %
7 5 %
1 0 0 %
2 5 %
5 0 %
7 5 %
1 0 0 %
ST
DB
Y
4.6
.2 Bypass mode setting
①
Enter the setting interface. Press and hold the function setting key
for more than 2 seconds, then come to
setting interface, press and hold the function setting key
for more than half a second(less than 2 seconds),
select the function setting, choose the bypass out
put interface, at the moment, the letters “BPS” will flash.
②
Enter the Bypass output setting interface. Press and hold the function setting key
for more than half a
second(less than 2 seconds), then come to setting interface of BPS, at this time, the letters “BPS” will not flash