manual pressure sensors
ipf electronic gmbh
Kalver Str. 25 - 27
58515 Lüdenscheid - Germany
www.ipf-electronic.
com
Subject to alteration!
Tel +49 2351 9365-0
Fax +49 2351 9365-19
info@ipf-electronic.
com
dAA
dAA
is active if in
Ou 2
an analogue signal was set.
Damping the analogue output
This function filters peak values of short duration or high fre-
quency.
dAA-value = response time. Period of time between the chang-
ing of the pressure and the analogue signal. ( unit, seconds).
FOUA
FOUA
is active if in
OU 2
an analogue signal was set.
Error signal of the analogue output.
The analogue output signal is <3,6mA or >22mA
(for 4-20/ 20-4 only)
EdA
Error display of the analogue output.
(for 4-20mA/ 20-4mA only)
noc 2
noc 2 is active if in Ou 2 a switching function is set.
Switching function of switching output S2:
no.2
(normally open)
nc.2
(normally closed)
dS 2
ds 2
is active if in
Ou 2
a switching function is set.
on delay timer function S2
dr 2
ds 2
is active if in
Ou 2
a switching function is set.
off delay timer function S2
HI
saving the max. pressure value of the system. The highest value
is dislayed.
= delete memory
LO
Saving the min. pressure value of the system. The lowest value
is displayed.
= delete memory.
COF
zero-point calibration
The internal measurand (operating value of the sensor) is offset
compared to the real measurand.
adjustment range: +/-10% of the measuring span.
ddIS
Damping of the display (Peak-Hold-Time)
FdIS
Dislpay functions:
rd
rotate display
Ph
peak-hold. Temporary display of peak values
Rd.
Ph
rotate d peak hold
oFF
standard display