Configuration of output1:
Four switching functions are possible:
SP.HY
switching point / hysteresis
SP.rP
switching point / release point
FE.HY
window function / hysteresis
FE. rP
window function
/ release point
oFF.1
output 1 „off“
noc 1
noc 1
is active if in
Ou 1
a switching function is set.
Switching function of switching output S1:
no.1
(normally open)
nc.1
(normally closed)
ds 1
ds 1
is active if in
Ou 1
a switching function is set.
on delay timer function S1
dr 1
ds 1
is active if in
Ou 1
a switching function is set.
off delay timer function S1
Ou 2
Configuration output 2:
Four switching functions, the error signal or four analogue func-
tions are possible:
SP.HY
switching point / hysteresis
SP.rP
switching point / release point
FE.HY
window function / hysteresis
FE. rP
window function
/ release point
Err. 2
error signal
4-20
analogue signal 4-20mA
0-20
analogue
signal 0-20mA
20-4
analogue signal 20-4mA
20-0
analogue signal 20-4mA
oFF.2
output 2 „off“
ASP
ASP
is active if in
Ou 2
an analogue signal was set.
Analogue starting point:
The pressure value (low pressure) where the analogue output
starts.
AEP
AEP
is active if in
Ou 2
an analogue signal was set.
Analogue end point:
The pressure value (higher pressure), where the analogue sig-
nal ends.
Note:
The minimum range between starting point and end point
is 20% of the measuring range for the DW35 type; and 50% of
the measuring range for the DW36 type.