BMA_77024-o16m-05_Rev2_en 

IPAS GmbH, Hölscherstraße 27, D-47167 Duisburg 

[email protected] 

Operating- and mounting instructions 

PowerBlock o16 Multi 
Order number: 77024-180-05 

 

General usage 

 
Power Block series consists of 4 different devices types. It can be 
installed in a standard distribution board. 
 

 

only 4 DIN Rail modules for 4 outputs and 6 inputs 

 

only 4 DIN Rail modules for 8 outputs 
(Binary/Shutter/Blind/Fan Coil) 

 

only 8 DIN Rail modules for 16 outputs 
(Binary/Shutter/Blind/Fan Coil) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
A brief overview of the functionality is given in the following table: 

 

 
 

Device type and accessories 

 
At present the following device types are available in the PowerBlock 
control group: 
 

Product 

Description 

Order number:

PowerBlock o8 

8 capacitive outputs

77024-180-01

PowerBlock o8m 

8 capacitive outputs

77024-180-04

PowerBlock o16 

16 capacitive outputs 

77024-180-02

PowerBlock o16m 

16 capacitive outputs 

77024-180-05

PowerBlock io64 

4 capacitive o 
6 analog / digital inputs 

77024-180-03 

InBlock 

8 x 230VAC inputs

7704-180-30

Scope of delivery 

 
The following individual components are included in the delivery of the 
PowerBlock device: 
 

Complete device with connected bus connector 

Operating and mounting instructions 

1x heat shrinkable tubing 1.2 x 2cm for additional insulation 
of the bus cable 

Delivered in break-proof individual packaging 

 
 

Application programs 

 
The following application programs are currently available for the 
PowerBlock device: 
 

77014-PowerBlock o16m-22-0110 

 

Installation device 

 

 

 

 
Risk of death by electric shock.  

 

The device is intended for interior installation in dry rooms. 

 

The device must only be installed and commissioned by an 
accredited electrical engineer. 

 

When planning and construction of electrical installations, the 
national guidelines, rules and regulations of the country in quest-
ions are to be obeyed, as well as all current KNX guide lines. 

 

For the installation the device must be switched to zero potential. 

 

The device must not be opened.  

 

Any faulty devices are to be sent together with a return delivery 
to the manufacturer. 

 
 

Technical data 

 

POWER AND OUTPUTS SPECIFICATIONS 

Power supply 

 

Supply Voltage: 
Max. Consumption: 
Additional power 
supply:

21..30VDC 
9,4mA  
 
No

Number of 
outputs

Contacts: 

16 Dry contact 
(potential-free)

Output 
configuration 

 

Up to 16 outputs 
Up to 8 channels 
Up to 4 Fan Coil  
controllers

Output nominal 
values 

 

AC rated current / 
voltage: 
DC rated current / 
voltage:

16A / 250VAC 50/60Hz  
C-Loads max. = 140 µF 
 
16A / 30VAC

Device nominal 
values

Current / Voltage 

16A /250VAC per Output 

Phases switching 
distribution

 

1 independent phase 
allowed per output

Output life 
expectance 

Mechanical: 
 
Electrical: 

3𝑥10

 operations (at 60 

times/min) 

4𝑥10

 cycles with 

resistive load at maximal 
current

Connections 

KNX bus connection 
terminal: 
Terminal screw block: 
Tightening torque for 
terminal screw: 

 
0,8 mm Ø solid 
max. 6 mm Ø solid 
 
maximum 0.6 Nm

GENERAL SPECIFICATIONS 

Control and 
display elements 

 

Programming button: 
 
LED, red: 
 
16 x buttons: (for 
manual channels 
control) 
 
16 x LEDs, red: 

To assign the physical 
address. 
Displays addressing mode 
 
To switch On/Off outputs / 
Move Up/Down channels / 
Select Fan Speed / switch 
valve output. 
To display actual 
outputs/channels status

Outputs 
BINARY (POWER LEDs 
SUPPORTED) 

SHUTTER / BLIND 

Bus failure 

Bus failure 

Central ON/OFF 
Counters  
Scenes 
Timers 
Alarms 
Disable function 
Manual control 
 

Scenes 
Presets 
Alarms 
Disable function 
Manual control 
Façade control 
Shutter slits control 
True height positioning for 
shutter/blind 
 

ADVANCED FUNCTIONS 

FAN COIL (FC) 

Analog & digital alarms 

Fan Auto/Manual 

Scene controler 
Timers (with cyclic sending of 
time remaining 
Overwrite end user parameters 
Logic functions 
Setpoints 
Behaviour at bus recovery 

Operation modes (Fan & Valve 
restrictions) 
Manual fan speed with multiple 
DPTs obj. 
Remaining time to change filter 
Fan speed timers/delays/cyclic 
Scenes and Day & Night object 
Purge valve 
Thermostat monitoring 
Alarms 
 

Summary of Contents for PowerBlock o16 Multi

Page 1: ... all current KNX guide lines For the installation the device must be switched to zero potential The device must not be opened Any faulty devices are to be sent together with a return delivery to the manufacturer Technical data POWER AND OUTPUTS SPECIFICATIONS Power supply Supply Voltage Max Consumption Additional power supply 21 30VDC 9 4mA No Number of outputs Contacts 16 Dry contact potential fr...

Page 2: ...indicated on the casing To connect the KNX cable a standard bus connector is plugged into the respective entry on the device Please make sure that there is double basic insulation between the KNX installation and the power supply To do so please insulate the wires of the KNX cable up to the bus connector with the enclosed shrinkable tubing Please make sure that the cables are laid in a way that en...

Page 3: ...command to the Stop object LED blinks while moving UP DOWN during parameterized time Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time ...

Page 4: ...dicates channel status Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time o LED ON indicates the actual Fan Speed active o LED OFF indic...