OUTPUT SCHEMATIC 
 
Each channel can be configured to be used as 2 binary outputs or as 
one blind channel. In case Fan Coil controller is selected, 4 outputs will 
be used. Each output can be powered by an independent phase. 
 

 

 
 
 

ANNEX 1: Manual Control 

 

Attention: 

This option is activated after ETS Download. In delivery 

status this option is not available. 
 
The Power Block actuator has 2 push buttons and 2 status LEDs for 
each channel on the front side. These buttons can be activated to 
control each and every channel/output individually if you select “yes” in 
the relevant parameter options in Binary outputs / Shutter/Blinds / Fan 
Coil. The LEDs are arranged in two rows, whereas the LEDs 
represent: 
 

For Binary outputs 

 

The top row: channels A1,A2,B1,B2,C1,C2,D1,D2

 

 

The bottom row: channels E1,E2,F1,F2,G1 G2,H1,H2 

 

For Shutter/blinds:  

 

The top row: channel's first relay A1->UP, 
 A2->DOWN, B1-UP, etc. 

 

The bottom row: channel's second relay C1->UP,  
C2-> DOWN, D1-> UP, etc. 

 

For Fan Coil:

  

 

The top row:  

FC1: Fan Speed = Fan 1 (A1),  
Fan 2 (A2), Fan 3 (B1) // Output valve = B2. 

FC2: Fan Speed = Fan 1 (C1),  
Fan 2 (C2), Fan 3 (D1) // Output valve = D2. 
 

 

The bottom row:  

FC1: Fan Speed = Fan 1 (E1),  
Fan 2 (E2), Fan 3 (F1) // Output valve = F2. 

FC2: Fan Speed = Fan 1 (G1),  
Fan 2 (G2), Fan 3 (H1) // Output valve = H2. 

 

MANUAL CONTROL – PARAMETER 
 
The Parameter Mode allows you to control all the channels of the 
actuator as configured in the ETS. The Action simulates a telegram 
received at the switching object of the selected channel. 
 

BINÄRY

SHUTTER/BLIND

Press action: Sends Toggle 
ON/OFF command “0/1” to the 
“Switching” object. 

 
 
 

 LED = ON (indicates 

channel status) 
 
 
 
 
 

 LED = OFF (indicates 

channel status) 

Long press action (Channel 
output 1):  
Sends a UP command “0” to the 
“Move” object. 
Long press action (Channel 
output 2):  
Sends a DOWN command “1” to 
the “Move” object. 
 
Short press action (any output) 
(while shutter/blind is moving) of 
same button:  
Sends a Stop command to the 
“Stop…” object. 
 

 LED blinks while moving 

UP/DOWN during parameterized 
time. 

 
 

Fan Coil 

 
Valve press action:

 

Sends toggle ON/OFF command to the relay (ON 

= Contact closed / OFF = Contact open) 
 
Fan speed press action:

 

Actives the selected Fan Speed switching the 

corresponding relays, depending of the configuration Fan Coil Type 
(Single or Multiple)

  

 

Type of Fan Coil = Single (Only one output can be ON at time) 

o

 

LED = ON (indicates the actual Fan Speed active) 

o

 

LED = OFF (indicates the actual Fan Speed is not active) 

 
Type of Fan Coil = Multiple (Switch outputs sequentially ON) 

o

 

LED = ON (Accumulated ON status, it indicates the actual 
Fan Speed active) 

o

 

LED = OFF (indicates the actual Fan Speed is not active) 

 
 
MANUAL CONTROL – TEST 
 
The Test Mode allows you to test all the loads/wiring connected to the 
channels. It is independent from the ETS configuration of the actuator 
(since the “Manual Control / Param mode + Test mode” is a default 
option, you can use the Test mode even before programming the 
actuator). 
 
Important note: Should a blind/shutter be connected to a channel, the 
2 channels may never be closed at the same time. Therefore, even in 
Test mode, if the channel is configured as a blind, this safety measure 
is implemented. For this reason, it is better to first commission the 
OUTPUT: CHANNEL TYPE SELECTION before using the Test mode. 
 
To change into the test mode, any button can be used depending of 
the channel configuration: 
 
 - If “Binary” or” Fan Coil” channel is configured: Press any button for 
   at least 500ms  
 - If “Blind” channel is configured: Press the two buttons of any channel 
   at the same time for at least 500ms 
 
To change back to the normal “Parameter Mode” the same procedure 
should be repeated. Be aware by changing back to “Parameter Mode” 
the device will restart. Also after the device has restarted and if the 
channel is configured to be a blind channel, it will do a calibration 
movement on the first movement command.  
 

 In order to indicate that the actuator is in Manual Control / Test 

Mode, the LED of the selected channel is continuously making a short 
blinking action every second; no matter whether the channel is ON 
(LED ON) or OFF (LED OFF).

 

Summary of Contents for PowerBlock o16 Multi

Page 1: ... all current KNX guide lines For the installation the device must be switched to zero potential The device must not be opened Any faulty devices are to be sent together with a return delivery to the manufacturer Technical data POWER AND OUTPUTS SPECIFICATIONS Power supply Supply Voltage Max Consumption Additional power supply 21 30VDC 9 4mA No Number of outputs Contacts 16 Dry contact potential fr...

Page 2: ...indicated on the casing To connect the KNX cable a standard bus connector is plugged into the respective entry on the device Please make sure that there is double basic insulation between the KNX installation and the power supply To do so please insulate the wires of the KNX cable up to the bus connector with the enclosed shrinkable tubing Please make sure that the cables are laid in a way that en...

Page 3: ...command to the Stop object LED blinks while moving UP DOWN during parameterized time Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time ...

Page 4: ...dicates channel status Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time o LED ON indicates the actual Fan Speed active o LED OFF indic...

Reviews: