BMA_77024-o16m-05_Rev2_en 

IPAS GmbH, Hölscherstraße 27, D-47167 Duisburg 

[email protected] 

Mechanical data 

REG casing 8TE: 
Width: 
Hight: 
Lenght: 
Weight 
Mounting: 

Plastic ABS – V0 
144 mm 
  58 mm 
  90 mm 
440 g 
35 mm DIN rail

Electrical safety 

Pollution class: 
Protection type:* 
Protection class:** 
Overvoltage category: 
KNX Bus: 


IP20 
III 
III 
SELV DC 30V

EMC 
requirements 

Complies with: 
 

EMC directive 2014/30/EU 

Environmental 
conditions 

Weather resistance: 
Environmental con-
ditions in operation: 
Storage emperature: 
Transportation 
temperature: 
Rel. humidity: 
(non condensing) 

EN 50090-2-2 
 
  -5°C to +45°C  
-25°C to +55°C 
    
-25°C to +70°C 
   5 % to 93 % 

Certification CE-
Signage 

  

KNX registered: 
According to EMC-
Guidelines: 

Yes 
(Residential and 
commercial buildings), 
Low Voltage guidelines

 
* (according to EN 60529); ** (according to IEC 1140) 
 
 
 

Location and function of the LEDs and control elements 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 
 
 
 

Mounting and wiring 

 
As an REG device, the Power Block series are suitable for mounting in 
distribution boxes on 35 mm DIN rails and wall boxes.  
 
To mount the device, it must be angled to slide onto the DIN rail from 
above and then locked into place with a downward movement.  
 
Please make sure that the security latch at the bottom side of the 
device snaps into place and that the device is firmly attached to the 
rail. To dismount the device, the security latch can be pulled 
downwards with a suitable tool and then the device can be removed 
from the rail.  
 
After the device has been inserted, the cables for the Outputs should 
be attached to the upper and lower connectors. However, please make 
sure that these are labelled clearly.  
 
The power supply is connected to the bottom right-hand side 
connector according to the order indicated on the casing. To connect 
the KNX cable, a standard bus connector is plugged into the 
respective entry on the device. Please make sure that there is double 
basic insulation between the KNX installation and the power supply.  
To do so, please insulate the wires of the KNX cable up to the bus 
connector with the enclosed shrinkable tubing.  
 
Please make sure that the cables are laid in a way that ensures 
sufficient distance between the inputs and outputs cables. 
 

 

 

4

6.1 

6.2 

2

1

7.3 

144mm / 8 DIN RAIL 

7.1 

7.2 

6.3 

6.4 

8

7.4 

1

: KNX bus connector 

2

: Programming button  

3

: Programming LED 

4

: SD card slot (only for internal use) 

5

: Outputs connector: Channel A, B, C, D 

 

6.1

: Manual control (See Annex 1) 

Blind channel:  
- Long press:  Move Up (LED blinks while moving) 
- Short press: Stop/Step 
Binary channel:  
- Short press: Output toggles to ON/OFF 
FC Fan Speed: 
- Short press: Fan Speed 1 is selected 
 

 

 

6.2

: Manual control (See Annex 1) 

Blind channel:  
- Long press:  Move Down (LED blinks while moving) 
- Short press: Stop/Step 
Binary channel:  
- Short press: Output toggles to ON/OFF 
FC Fan Speed:  
- Short press: Fan Speed 2 is selected 
 

6.3

: Manual control (See Annex 1) 

FC Fan Speed:  
- Short press: Fan Speed 3 is selected 
 

6.4

: Manual control (See Annex 1) 

FC Valve Output:  
- Short press: Output valve toggles to ON/OFF 
 

7.1

: LED output/channel status 

Binary channel: LED ON = Output ON, LED OFF = Output OFF 
Shutter: LED blinks while moving UP 
Fan Coil (Type of Fan = Single):  

LED ON = Fan Speed 1 ON 

LED OFF = Fan Speed 1 OFF 
 

7.2

: LED output/channel status 

Binary channel: LED ON = Output ON, LED OFF = Output OFF 
Shutter: LED blinks while moving DOWN 
Fan Coil (Type of Fan = Single):  

LED ON = Fan Speed 2 ON 

LED OFF = Fan Speed 2 OFF 

 
7.3

: LED output/channel status 

Fan Coil (Type of Fan = Single):  

LED ON = Fan Speed 3 ON 

LED OFF = Fan Speed 3 OFF 

 
7.4

: LED output/channel status 

Fan Coil (Valve Output):  

LED ON = Valve ON 

LED OFF = Valve OFF 

 
8

: Outputs connector: Channel E, F, G, H 

 

Summary of Contents for PowerBlock o16 Multi

Page 1: ... all current KNX guide lines For the installation the device must be switched to zero potential The device must not be opened Any faulty devices are to be sent together with a return delivery to the manufacturer Technical data POWER AND OUTPUTS SPECIFICATIONS Power supply Supply Voltage Max Consumption Additional power supply 21 30VDC 9 4mA No Number of outputs Contacts 16 Dry contact potential fr...

Page 2: ...indicated on the casing To connect the KNX cable a standard bus connector is plugged into the respective entry on the device Please make sure that there is double basic insulation between the KNX installation and the power supply To do so please insulate the wires of the KNX cable up to the bus connector with the enclosed shrinkable tubing Please make sure that the cables are laid in a way that en...

Page 3: ...command to the Stop object LED blinks while moving UP DOWN during parameterized time Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time ...

Page 4: ...dicates channel status Fan Coil Valve press action Sends toggle ON OFF command to the relay ON Contact closed OFF Contact open Fan speed press action Actives the selected Fan Speed switching the corresponding relays depending of the configuration Fan Coil Type Single or Multiple Type of Fan Coil Single Only one output can be ON at time o LED ON indicates the actual Fan Speed active o LED OFF indic...

Reviews: