OPERATION 

 

The  CD425  is  a  self  contained  low  temperature  dehumidifier.  All  electrical 
contactors, overloads, etc are housed in an electrical box built inside the unit. 
The  unit  is  equipped  with  a  defrost  valve  which  energized  automatically  to 
clear any ice formation on the evaporator coils. This allows the unit to operate 
at  much  lower  temperatures;  the  control  panel  gives  indication  of  the  set 
humidity, drying and defrost status. 
 
 
 
 
 
 
 
 
 
 
 

 
TEST FOR CORRECT OPERATION 
 

The  following  procedure  should  be  followed  to  test  the  unit  for  correct 
operation. 
 

1.  After unpacking connect the unit to a 220V 3PH 60 Hz power supply. 
2.   Switch  the  machine  to  the  on  position  and  check  for  correct  fan 

rotation.  (Air blows out of the top of the machine). 

3.  Check dehumidification process: 

a)  Remove front cover 
b)  Check actual relative humidity inside the area 
c)  Set  humidity  control  to  a  lower  value  than  the  actual  relative 

humidity as follows: 

i.  Press  the  UP  and  DOWN  arrow  keys  together  for  3 

seconds and the display will start to flash 

ii.  Use the UP and DOWN arrow keys to adjust the set point 

to 35% (Range is 35% - 99%) 

iii.  Press the RIGHT arrow key to save (if the RIGHT arrow 

key is not pressed for 3 seconds the selection is 
cancelled) 

iv.  Once set to 35% and saved the compressor will start and 

the drying light illuminates. 

d)  After approximately 6 minutes check the compressor is running. 
e)  Leave  the  machine  to  run  for  15  minutes.    (NOTE:  ensure  that 

the  set  humidity,  see  c)  above,  is  set  very  low  as  the 
compressor will switch off when the actual RH coincides with the 
set point) 
 
 

GREEN LENS 
POWER ON 

RED LENS 
POWER OFF 

BLUE LENS 
DEFROST 

YELLOW LENS 
DEHUMIDIFYING 

Summary of Contents for 10146BR-US

Page 1: ...Page 1 of 16 Drawing TPC572 Issue 1 Date 08 02 22 CD425 10146BR US INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...e 2 of 16 Drawing TPC572 Issue 1 Date 08 02 22 CD425 PACKAGE CONTENTS Item Description Quantity 10146BR US Dehumidifier 1 3086119 Jubilee clip 2 3014315 Reinforced tubing 16mm I D 2 X 3M TPC572 Manual...

Page 3: ...n tray for collecting and disposing of condensed moisture f A cabinet to house the above components The fan draws the moist air through the evaporator coils which cools the air below its dew point Moi...

Page 4: ...igerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data la...

Page 5: ...the CD425 s drain tray Failure to observe this requirement will result in internal flooding of the dehumidifier POSITIONING The CD425 is designed for indoor use only Position the dehumidifier unit in...

Page 6: ...lows out of the top of the machine 3 Check dehumidification process a Remove front cover b Check actual relative humidity inside the area c Set humidity control to a lower value than the actual relati...

Page 7: ...sed water should cover the entire evaporator coil 4 Leave the unit to run for approximately 42minutes from compressor starting after which the unit should go through a 4 minute defrost cycle During th...

Page 8: ...covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5...

Page 9: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 10: ...g diagram to find fault and repair Little or no water extraction 1 Insufficient air movement 2 Compressor fault 3 Loss of refrigerant gas 4 Blocked filter dryer 1 Check all of the above 2 Contact the...

Page 11: ...020835 1 Filter Dryer 3020930 1 Fan Motor 3030140 1 Contactor Fan 3030301 1 Contactor Compressor 3030321 1 Auxiliary contact Fan 3030322 1 Solenoid Coil 3030454 1 Transformer 3031144 1 Terminal Block...

Page 12: ...WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FO...

Page 13: ...d This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products man...

Page 14: ...Page 14 of 16 Drawing TPC572 Issue 1 Date 08 02 22...

Page 15: ...Page 15 of 16 Drawing TPC572 Issue 1 Date 08 02 22...

Page 16: ...state Bishop Auckland County Durham DL14 9AD Tel 44 0 1388 664400 Fax 44 0 1388 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite...

Reviews: