Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 4/16

 

UMA-CDZ-IP-ACOWM085-00

 

2 - INSTALLATION 

 
2.1  PRODUCT HANDLING 

 

AIR  CONDITIONER  IP-ACOW  series  must  be  handled  in  upright 
position and protected against accidental tipping over. 

 

Air conditioners IP-ACOW series are fitted with female blind threaded insert to screw male 
lifting eye bolts. 

 

The air conditioner handling, when unpacked, can be done thanks to lifting eye bolt.  
If lifting eye bolts are not included, please provide an adequate M6 male lifting eye bolt 

(2)

 

and screw it inside blind threaded 

(1)

 insert placed on top of the air conditioner.  

(For .0X version remove the rubber plugs placed on the top of AISI304 cover, they cover 
the threaded inserts)  

       

Check the proper fixing of eye bolts before lift the air conditioner. 

 

2.2  GENERAL CHECKS BEFORE INSTALLATION 

 
Before the installation make sure that the cabinet is disconnected from the 
electrical supply. 

 
GENERAL CHECKS 

-  electrical enclosure must be disconnected form power supply 
-  electrical data shown on rating label pasted on air conditioner side must be 

guaranteed 

-  Electrical enclosure must be sized according to air conditioner dimensions and 

weight. 

-  Electrical enclosure must have at least IP54 protection degree 
-  Internal and external components of electrical enclosure don’t have to affect the 

proper installation of air conditioner 

-  The installation site must be free from excessive dirt, aggressive ambient 

conditions and moisture. 

-  The installation site must be free from hot air flows  
-  The internal side of electrical enclosure must be free from dirt and moisture 
-  The environment temperature must be within the range specified on label pasted 

on air conditioner side 

-  Inside of electrical enclosure there must not be components that could affect the 

proper ventilation 

-  the enclosure positioning with installed air conditioner must be carefully selected to 

ensure good ventilation (clearance between the air conditioner and the near walls 
must be at least 500 mm in each side). 

-  Proper disposing of condensate discharge 

Summary of Contents for IP-ACOWM085

Page 1: ...00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM085 IP ACOWM085 0X Document UMA CDZ IP ACOWM085 00 Date Name Description Original user s manual for air con...

Page 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Page 3: ...IP ACOWM085 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 850 900 A35 A50 W 625 650 Absorbed electric power EN14511 A35 A35 W 490 530 A35 A50 W 600 640 Rated cu...

Page 4: ...ERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized accor...

Page 5: ...IR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM085 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accide...

Page 6: ...nscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because th...

Page 7: ...ush the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner si...

Page 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM085 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM085 IP ACOWM085 0X...

Page 9: ...minimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan tur...

Page 10: ...ide 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost...

Page 11: ...er selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting...

Page 12: ...rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFERRED TO WIRING DIA...

Page 13: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Page 14: ...E LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40...

Page 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM085 00 SAA CERTIFICATE...

Page 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM085 00 NOTES...

Reviews: