IP Enclosures IP-ACOWM085 User Manual Download Page 3

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 3/16

 

UMA-CDZ-IP-ACOWM085-00

 

TABLE OF CONTENTS 

 

WARNING .................................................................................................................................. 2

 

1 - TECHNICAL DATA ................................................................................................................... 3

 

2 - INSTALLATION ....................................................................................................................... 4

 

2.1

 

PRODUCT HANDLING .................................................................................................... 4

 

2.2

 

GENERAL CHECKS BEFORE INSTALLATION ..................................................................... 4

 

2.3

 

FITTING ........................................................................................................................ 5

 

3 - ELECTRICAL CONNECTION ...................................................................................................... 7

 

3.1

 

WIRING DIAGRAM ........................................................................................................ 8

 

3.1.1

 

IP-ACOWM085 / IP-ACOWM085.0X ....................................................................... 8

 

4 - STARTING AND ADJUSTMENT ................................................................................................ 9

 

4.1

 

DIGITAL THERMOSTAT .................................................................................................. 9

 

5 - SPARE PARTS LIST ................................................................................................................ 12

 

WARRANTY .............................................................................................................................. 13

 

UE DECLARATION OF CONFORMITY .......................................................................................... 14

 

SAA CERTIFICATE ...................................................................................................................... 15

 

 

1 - TECHNICAL DATA 

 

CONTROL TYPE 

ARTICLE CODE 

Digital thermostat

 

IP-ACOWM085 

IP-ACOWM085.0X 

FEATURES  

Unit 

 

Power supply 

V | ph| Hz 

230 | 1 | 50/60 

Cooling capacity EN14511 

A35-A35 

850/900 

A35-A50 

625/650 

Absorbed electric  

power EN14511 

A35-A35 

490/530 

A35-A50 

600/640 

     Rated current 

2.65/2.75 

Motor circuit breaker / Delayed pre fuse (advised) 

Electrical connection 

Three-pole connector 

Air flow rate (free blow) 

enclosure 

m3/h 

600/625 

Operating temperature 

ambient 

°C (°F) 

+5 |+55  (+41/+ 131) 

enclosure 

°C (°F) 

+20 |+45  (+68/+ 113) 

Refrigerant 

- | g 

R134a | 390 

Protection degree EN60529/1  

ambient 

IP34 

enclosure 

IP54 (when installed on enclosure with the 

same protection degree) 

Design 

casing 

Galvanised sheet steel 

cover 

Galvanised sheet steel 

powder coated 

RAL7035 

AISI304 

Weight 

kg 

23 

Conformity / Certifications 

CE, SAA

 

203165 

 

 

 
 

 

Summary of Contents for IP-ACOWM085

Page 1: ...00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM085 IP ACOWM085 0X Document UMA CDZ IP ACOWM085 00 Date Name Description Original user s manual for air con...

Page 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Page 3: ...IP ACOWM085 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 850 900 A35 A50 W 625 650 Absorbed electric power EN14511 A35 A35 W 490 530 A35 A50 W 600 640 Rated cu...

Page 4: ...ERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized accor...

Page 5: ...IR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM085 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accide...

Page 6: ...nscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because th...

Page 7: ...ush the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner si...

Page 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM085 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM085 IP ACOWM085 0X...

Page 9: ...minimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan tur...

Page 10: ...ide 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost...

Page 11: ...er selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting...

Page 12: ...rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFERRED TO WIRING DIA...

Page 13: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Page 14: ...E LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40...

Page 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM085 00 SAA CERTIFICATE...

Page 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM085 00 NOTES...

Reviews: