Using Multiple Inputs to Control One DAC Output
Update Mode: Rising Edge, for each of 2 channels
Criteria Used: Inside Window, for each of 2 channels
The figure below shows how multiple inputs can update one output. In the following figure the DAC2
analog output is being updated. Analog input Channel 3 has an
inside-the-window
setpoint applied.
Whenever Channel 3’s input goes inside the programmed window, DAC2 will be updated with 3.0V.
Analog input Channel 7 also has an
inside-the-window
setpoint applied. Whenever Channel 7’s input goes
inside the programmed window, DAC2 will be updated with
minus
7.0V.
Limit A
(for Ch3)
Limit B
(for Ch3)
Limit A
(for Ch7)
Limit B
(for Ch7)
Detection (Ch3)
Detection (Ch7)
+3.0 V
DAC2 0.0 V
-7.0 V
Using Two Criteria to Control an Output*
*
The update
on True Only
mode was selected and therefore the updates for DAC2 will only occur when the criteria is
met. However, in the above figure we see that there are 2 setpoints acting on one DAC. We can also see that the two
criteria can be met simultaneously. When both criteria are
True
at the same time, the DAC2 voltage will be associated
with the criteria that has been most recently met.
6-10 Setpoint Configuration for Output Control
908794
DaqBoard/3000 Series User’s Manual
Summary of Contents for DaqBoard/3000 Series
Page 2: ...ii...
Page 6: ...vi DaqBoard 3000 Series User s Manual...
Page 16: ...IG 8 DaqBoard Installation Guide 918494 1033 0940 rev 8 0...
Page 38: ...2 8 Connections Pinouts 918494 DaqBoard 3000 Series User s Manual...
Page 42: ...4 2 Calibration 918494 DaqBoard 3000 Series User s Manual...
Page 82: ...6 12 Setpoint Configuration for Output Control 908794 DaqBoard 3000 Series User s Manual...
Page 104: ...DBK215 pg A 14 948894 Appendix A...
Page 106: ...B 2 Hardware Analog Level Trigger 90794 Appendix B...