Page 4
Rev. 2205
912-00066-001
ILBLP CP HE SD HV WITH TBTS TEST ACCESSORY
ILBLP20-30_TBTS.EPS
AC (NORMAL)
DRIVER
IOTA ILBLP
EMERGENCY DRIVER
LED
LOAD
WHITE
WHITE
WHT/RED
NEUTRAL
UNSWITCHED
24/7 POWER
BLACK (120 TO 277V, 50/60HZ)
AC INPUT (120 TO 277V)
SWITCHED OR
UNSWITCHED
HOT
RED (+)
BLUE (-)
VIOLET/WHITE (+)
LED INPUT(-)
LED INPUT (+)
LED OUTPUT (+)
LED OUTPUT (-)
YELLOW
BROWN
LEDCODE (+)
LEDCODE (-)
TBTS
TEST ACCESSORY
!
Cap unused
LEDCODE wires
CONDITION
STATUS INDICATION
STEADY GREEN
BATTERY IS FULLY CHARGED
STEADY RED
BATTERY IS CHARGING
FLASHING GREEN
UNIT IS PERFORMING A TEST
OFF
EMERGENCY MODE
FLASHING RED/GREEN
INSUFFICIENT CHARGE
1 RED FLASH
BATTERY FAILURE
2 RED FLASHES
EMERGENCY LED LOAD FAILURE
3 RED FLASHES
ELECTRONICS FAILURE
4 RED FLASHES
TEMPERATURE OUT OF RANGE
TESTING & MAINTENANCE
Automatic Testing
The
ILBLP CP HE SD HV
is designed to automatically test
the emergency function for 60 seconds each month, and
90 minutes every 12 months.
Self-testing works in conjunction with the TBTS assembly.
Any detected failures will be indicated by flashing of its
bi-color LED. See Table A for diagnosis:
Manual Testing
Manual testing of the
ILBLP CP HE SD HV
can be performed
by pressing and holding the TBTS test button for two seconds.
Only initiate a manual test when the TBTS status indicator light
is GREEN (see
Table A
). Manual testing lasts 60 seconds and
may be cancelled at any time during the test duration by press-
ing and holding the TBTS for at least two seconds.
Table A:
TBTS Diagnostic Codes
WIRING DIAGRAM
Refer to the diagram below for the appropriate wiring of the LED load and driver. Install in accordance with the National Electrical
Code and local regulations. For additional wiring diagrams consult Customer Service.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
Load Calibration
To ensure proper operation, Load Calibration is required whenever the LED load connected to the ILBLP CP HE SD HV is
changed.
Note:
Load Calibration happens automatically 48 hours after the ILBLP CP HE SD HV is first installed.
If after instal
-
lation,
the connected LED load is changed
,
Load Calibration will need to be performed
. This will happen
automatically
48 hours after the ILBLP CP HE SD HV is re-initialized (see Maintenance section below). To
manually
initiate Load Calibration
earlier, press and hold the TBTS button for 20 seconds. After 20 seconds, the LED load will turn off. Release the TBTS button.
The LED load should turn back on and the TBTS will begin FLASHING GREEN to indicate that the 60-second Load Calibration is
commencing. Any failures detected during Load Calibration will be indicated on the TBTS (see
Table A
).
Maintenance
When performing maintenance on the
ILBLP CP HE SD HV or the emergency luminaire
, the
ILBLP CP HE SD HV
battery
circuit must be completely powered down by performing the following steps:
1) Disconnect AC power.
The ILBLP CP HE SD HV will enter EMERGENCY MODE.
2) Disconnect the battery circuit through one of the following methods:
Method 1:
This can only be performed within the first 30 seconds of EMERGENCY Mode -
Press and hold the TBTS button
for approximately five seconds until the LED Module shuts off.
Method 2:
Unplug the TBTS
Once all power sources are disconnected from the
ILBLP CP HE SD HV
and
emergency luminaire
, proceed with required
maintenance.
When
maintenance is complete
, reconnect the TBTS (if unplugged) and restore AC power to the emergency luminaire. The AC
Activate circuitry will detect the presence of AC power and automatically re-activate the
ILBLP CP HE SD HV
battery charging
circuit.