background image

Page 2

FLEX 

CEILING

TILE

LED DRIVER AND ARRAY 

COMPARTMENT

TBTS

Lorem ipsum

STEP 1 - 

MOUNTING THE ILBLP CP HE SD HV

The 

ILBLP CP HE SD HV

 should be mounted on or nearby the 

fixture above the ceiling. The flex conduit should be wired into 

the driver/lamp compartment or to an electrical junction box on 

the fixture which allows access to the fixture connections.

TBTS

ILBLP CP HE SD HV

SPECIFICATIONS - 

Illustration 1

Model

ILBLP CP20 ... HV

ILBLP CP30 ... HV

Output Voltage (Min - Max)

40-200 VDC

40-250 VDC

Minimum Operation

90 Minutes

90 Minutes

Input Voltage (Min - Max)

120-277 VAC

120-277 VAC

INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain A.C. power is off and the Threaded Body Test Switch (TBTS) is disconnected.

STEP 3 - 

INSTALLING THE THREADED BODY TEST SWITCH (TBTS)

A.  Locate a suitable location for the TBTS 

and cable that is visible outside the fixture. 

Drill or punch a 1/2” diameter hole in the 

luminaire wall or wireway cover. Insert the 

TBTS into the hole so that the LED test 

button is located outside of the fixture. 

B.  Secure the TBTS against the 

luminare housing by screwing 

on the TBTS nut.

C.  Connect and fully engage the TBTS 

Connector to the TBTS Socket. Ensure the 

TBTS Connector is properly seated in the 

TBTS Socket, then mark the TBTS location 

on the switch box plate with the TBTS Label 

and apply the SD Status Indicator Sticker. 

FLEX 

CEILING

TILE

LED DRIVER AND ARRAY 

COMPARTMENT

TBTS

Lorem ipsum

TBTS

ILBLP CP HE SD HV

LUMINAIRE HOUSING

LUMINAIRE HOUSING

TBTS NUT

TBTS NUT

Remote Mounting

 - The TBTS may be remote mounted from the fixture up to 25 feet. 

Before extending the TBTS wires, 

ensure that AC Power is off and the TBTS has been disconnected.

 To extend the TBTS wires, splice the TBTS leads 

between the test switch and connector and install a patch cable (minimum 18 AWG) of the desired length to the spliced ends. 

Be sure to observe wire color. After extending the TBTS wires, follow the installation procedure (steps A, B, and C) above to 

recconnect the TBTS.

STEP 2 - 

WIRING TO THE LED LOAD AND NORMAL DRIVER

ILB-LP NORMAL DRIVER AND LED LOAD CONNECTIONS

ilbcp_tspl_normal-driver-and-load-only.eps

AC (NORMAL) 

DRIVER

IOTA ILBLP

EMERGENCY DRIVER

LED

LOAD

WHITE

WHT/RED

RED (+)
BLUE (-)

YELLOW
BROWN

LEDCODE (+)
LEDCODE (-)

VIOLET/WHITE (+)

 LED INPUT(-)

 LED INPUT (+)

 LED OUTPUT (+)

 LED OUTPUT (-)

!

Cap unused  

LEDCODE wires

Refer to the appropriate wiring diagram below. Make sure all connections are in accordance with NEC and any other 

 

local requirements. 

The ILBLP CP HE SD HV is designed to interface with high voltage (non-class 2) LED Loads. 

See 

Illustration 1

 for output voltage ratings per ILBLP model.

Summary of Contents for ILBLP CP10 HE SD

Page 1: ...should be performed by qualified personnel only De energize before opening 6 The ILBLP CP HE SD HV is for use with grounded LED luminaires listed to UL standards Not for use in heated air outlets or hazardous locations 7 The ILBLP CP HE SD HV and A C driver must be on the same branch circuit 8 Do not mount near gas or electric heaters 9 The ILBLP CP HE SD HV should be mounted in locations and at h...

Page 2: ...erly seated in the TBTS Socket then mark the TBTS location on the switch box plate with the TBTS Label and apply the SD Status Indicator Sticker FLEX CEILING TILE LED DRIVER AND ARRAY COMPARTMENT TBTS Lorem ipsum TBTS ILBLP CP HE SD HV LUMINAIRE HOUSING L U M I N A I R E H O U S I N G T B T S N U T TBTS NUT Remote Mounting The TBTS may be remote mounted from the fixture up to 25 feet Before extend...

Page 3: ...d allow the unit to charge for at least 1 hour before performing a functional test B Verify that the TBTS light is on The lamp will illuminate Red while the battery is charging and Green when the battery is fully charged C Press and hold the TBTS button for two seconds The pilot light will blink Within five seconds the LED Module should be operating at a reduced light output The test mode runs for...

Page 4: ...r inspection by the authority having jurisdiction SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service or visit www iotaengineering com for current warranty information Load Calibration To ensure proper operation Load Calibration is required whenever the LED load connected to the ILBLP CP HE SD HV is changed Note Load Calibration happens automatically 48 hours after the IL...

Page 5: ... CP HE SD HV est conçu pour être utilisé avec des luminaires à DEL mis à la terre homologués UL Ne pas utiliser avec des prises d air chauffées ou dans des endroits dangereux 7 Le pilote ILBLP CP HE SD HV et c a doit être sur le même circuit de dérivation 8 Ne pas installer à proximité d appareils de chauffage au gaz ou électriques 9 L ILBLP CP HE SD HV doit être installé à des endroits et à des h...

Page 6: ...rges LED haute tension non classe 2 Voir l illustration 1 pour les tensions nominales de sortie par modèle ILBLP ÉTAPE 3 INSTALLER LE COMMUTATEUR DE TEST DU CORPS FILETÉ TBTS A Trouvez un emplacement satisfaisant pour la TBTS et le câble qui est visible à l extérieur du luminaire Percez ou défoncez un trou d un diamètre de 1 2 po dans la paroi du luminaire ou dans le couvercle du chemin de câbles ...

Page 7: ... alimentation secteur fait fonctionner le module DEL comme prévu L ILBLP CP HE SD HV est en mode de chargement en veille Le TBTS est allumé et indique de manière visuelle que la batterie est en cours de chargement Mode d urgence L alimentation secteur tombe en panne L ILBLP CP HE SD HV détecte la panne de courant et bascule automatiquement en mode d urgence Le module DEL est allumé et la sortie es...

Page 8: ...inq secondes jusqu à ce que le module à DEL s éteigne Méthode 2 Débranchez le TBTS Une fois que toutes les sources d alimentation sont débranchées du luminaire ILBLP CP HE SD HV et du luminaire d urgence procéder à l entretien requis Une fois l entretien terminé rebrancher le TBTS si débranché et rétablir l alimentation c a au luminaire d urgence Le circuit AC Activate détectera la présence d une ...