background image

Page 2

VERIFYING COMPATIBILITY

The ILB CP18 HE CW can be used with most LED loads that operate at 20-58 VDC up to a load rating of  
18 Watts.

1. The ILB CP18 HE CW series has been evaluated to and found compliant to UL standard 924. The as-installed performance 

of system must meet or exceed all Federal, State, and Local code requirements.

2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels.

CAUTION:   Before installing, make certain A.C. power is off and the IP Rated Test Switch (IPS) 
is disconnected.

STEP 1 - 

MOUNTING THE ILB CP18 HE CW

Mount the 

ILB CP18 HE CW

 in the driver/lamp compartment or enclosed wireway so the wire leads are not 

exposed, at least ½

 

away from the AC Driver.

Remote Mounting: 

When the 

ILB CP18 HE CW 

is remotely mounted, consult Customer Service for the maximum 

allowable distance between the battery pack and the load.

Once the battery is secure

, connect the battery to the unit using the 

provided connection wires.

Do NOT install SLA batteries upside down.

The battery must be mounted securely. 

If the luminaire doesn’t include 

accessories to secure the battery within the luminaire housing, see 

page 5 

- Recommended Battery Installation Method for Luminaires Without Battery 
Installation Accessories.

Never charge or discharge a SLA battery 
in a hermetically sealed enclosure. 

When 

installing in sealed and gasketed luminaires, 
a method of proper venting must be 
incorporated. Do not place batteries in close 
proximity to objects that can product sparks.

INSTALLATION INSTRUCTIONS

STEP 2 - 

WIRING TO THE LED LOAD AND NORMAL DRIVER

Refer to the appropriate wiring diagram below. Make sure all connections are in accordance with NEC and any other  

local requirements.

ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - WIRING TO LOAD AND NORMAL DRIVER

ILB CP CW 1LA.EPS

AC (NORMAL) 

DRIVER

IOTA ILB CP CW

EMERGENCY DRIVER

LED

LOAD

BLACK

BLACK/WHITE

RED (+)
BLUE/WHITE (-)

RED/WHITE (+)

 LED INPUT(-)

 LED INPUT (+)

 LED OUTPUT (+)

 LED OUTPUT (-)

ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - BATTERY CONNECTIONS

ILB CP CW 1LA.EPS

IOTA ILB CP CW

EMERGENCY DRIVER

BATTERY

RED (+)

BLA

CK(-)

BATTERY (-)

BATTERY (+)

UNIT CONNECTOR

STEP 3 - 

INSTALLING THE BATTERIES

Reviews: