Page 2
IIS_550-HE_normally-on.EPS
INVERTER - ALWAYS ON FIXTURE
WHITE
ORG/BLK (120 / 277V)
COMMON
120 / 277V
WHITE/BLU (NEU)
GREEN
GROUND
GRAY
VIO/YEL
NEUTRAL
120 / 277V
(CIRCUIT MUST BE ISOLATED
FROM NORMAL CIRCUITS)
EMERGENCY LOAD
LINE
BLK (120 / 277V)
1
NORMAL AC INPUT -
“FLYING LEADS”
(UNSWITCHED)
OUTPUT
INVERTER AC INPUT -
“INPUT LEADS”
(UNSWITCHED)
IIS INVERTER
2
3
INVERTER AC INPUT (1) AND NORMAL
AC INPUT (2) LEADS MUST BE FED
FROM THE SAME BRANCH CIRCUIT.
Wiring
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off.
NOTE:
The battery is shipped in separate packaging for ease of handling. Store the battery in a cool, dry and safe
location until ready for installation. The battery may be kept in storage for up to 3 months without recharging.
CAUTION:
This is a universal input and output voltage unit. It can be connected to a 120 - 277 volt supply.
The input and output voltages must match
.
Mounting the IIS-550-HE
1) Remove the front cover of the
IIS-550-HE
by removing the two (2) screws located at the top of cover.
2) Knock out the keyhole slots in the rear of the unit and use for mounting the
IIS-550-HE
securely to the wall. After removing the
keyholes, hang the unit on two 1/4”-20 screws (Grade 2 or better) attached to the wall studs. An additional pair of 1/4”-20 screw holes
are provided underneath the electronics shelf. Code requires that additional screws be used through these holes to prevent the unit
from being inadvertently lifted up off the keyhole slots.
Do not drill any holes in this unit
.
3)
Extend an unswitched AC supply, switched AC supply (if used), and the load wires to the unit. 1/2
″
conduit knockouts are provided in
the top, back and sides of the unit for wires to pass through. NOTE: Input and output wires must be run in separate conduits.
CAUTION
:
Do not drill holes into the cabinet; drill filings may damage the unit and keep it from operating.
CAUTION: The IIS-550-HE must be mounted securely. Do not rely on the junction box for supporting the weight of the unit.
Mount the IIS-550-HE securely to the wall using the keyhole slots provided, or mount it on a secure platform.
ALWAYS CONSULT LOCAL CODES FOR STRUCTURAL REQUIREMENTS WHEN MOUNTING THE UNIT.
FIGURE 1 -
IIS-550-HE WIRING CONNECTIONS
IIS_550-HE_switched.EPS
INVERTER - SWITCHED FIXTURE
WHITE
ORG/BLK (120 / 277V)
COMMON
120 / 277V
WHITE/BLU (NEU)
GREEN
GROUND
GRAY
VIO/YEL
NEUTRAL
120 / 277V
(CIRCUIT MUST BE ISOLATED
FROM NORMAL CIRCUITS)
EMERGENCY LOAD
LINE
BLK (120 / 277V)
1
NORMAL AC INPUT -
“FLYING LEADS”
(SWITCHED)
OUTPUT
INVERTER AC INPUT -
“INPUT LEADS”
(UNSWITCHED)
2
3
WALL SWITCH
IIS INVERTER
INVERTER AC INPUT (1) AND NORMAL
AC INPUT (2) LEADS MUST BE FED
FROM THE SAME BRANCH CIRCUIT.
IIS_550-HE_em-only.EPS
INVERTER - EMERGENCY OPERATION ONLY
WHITE
ORG/BLK (120 / 277V)
COMMON
120 / 277V
WHITE/BLU (NEU)
GREEN
GROUND
GRAY
VIO/YEL
NEUTRAL
120 / 277V
(CIRCUIT MUST BE ISOLATED
FROM NORMAL CIRCUITS)
EMERGENCY LOAD
LINE
BLK (120 / 277V)
1
NORMAL AC INPUT -
“FLYING LEADS”
(UNSWITCHED)
OUTPUT
INVERTER AC INPUT -
“INPUT LEADS”
(UNSWITCHED)
2
3
CAP UNUSED
LEADS
IIS INVERTER
INVERTER AC INPUT (1) AND NORMAL
AC INPUT (2) LEADS MUST BE FED
FROM THE SAME BRANCH CIRCUIT.
- ALWAYS ON FIXTURES
Fixtures are used for both normal and
emergency power conditions. During
a loss of normal AC power, the IIS
automatically senses the drop in line
voltage, and powers the fixtures with its
internal battery.
- SWITCHED FIXTURES
Fixtures are used for both normal and
emergency power conditions, and are
controlled by a local switching device.
During a loss of normal AC power, the
IIS automatically senses the drop in line
voltage, and powers the fixtures with
its internal battery, regardless of the
position of the switching device.
- NORMALLY OFF FIXTURES
Fixtures on the emergency circuit are
used in emergency mode only, and
are not energized during normal power
conditions (Note: Normal AC Input leads
are not connected).