CONTROL AND REGULA
CONTROL AND REGULA
CONTROL AND REGULA
CONTROL AND REGULA
CONTROL AND REGULATION
TION
TION
TION
TION
PCB : Centralised control module management module
T1
: 400/230V single phase transformer
ST1 : Inlet water temperature sensor
ST2 : Outlet water temperature sensor
ST3 : Condensing temperature sensor
ST4 : Outdoor air temperature sensor
SM1 : ON/OFF switch in casing
OCT: Condenser temperature sensor (Heat pump models)
NOT PROVIDED :
NOT PROVIDED :
NOT PROVIDED :
NOT PROVIDED :
NOT PROVIDED :
SD/N : Day / night changeover
SLS
: Load-shedding switch
RANGE AND SETTINGS OF THEMAL PRO
RANGE AND SETTINGS OF THEMAL PRO
RANGE AND SETTINGS OF THEMAL PRO
RANGE AND SETTINGS OF THEMAL PRO
RANGE AND SETTINGS OF THEMAL PROTECTION / NOMINAL INTENSITY OF THE
TECTION / NOMINAL INTENSITY OF THE
TECTION / NOMINAL INTENSITY OF THE
TECTION / NOMINAL INTENSITY OF THE
TECTION / NOMINAL INTENSITY OF THE
CONT
CONT
CONT
CONT
CONTA
A
A
A
ACT
CT
CT
CT
CTORS (CLASSE A
ORS (CLASSE A
ORS (CLASSE A
ORS (CLASSE A
ORS (CLASSE AC3)
C3)
C3)
C3)
C3)
25
30
35
40
50
60
range
9 - 14 A
9 - 14 A
13 - 18 A
13 - 18 A
20 - 25 A
20 - 25 A
Adjustment
10 A
11.5 A
13 A
16 A
21 A
23 A
range
9 - 14 A
9 - 14 A
9 - 14 A
13 - 18 A
13 - 18 A
13 - 18 A
Adjustment
10 A
11.5 A
11.5 A
13 A
13 A
16 A
range
1.6 – 2,5 A
1.6 – 2.5 A
1.6 – 2.5 A
1.6 – 2.5
1.6 – 2.5
2.5 - 4 A
Adjustment
1.7 A
1.7 A
1.7 A
2.1 A
2.1 A
3.1 A
range
6 – 10 A
6 – 10 A
6 – 10 A
6 - 10 A
9 - 14 A
9 - 14 A
Adjustment
6.3 A
6.3 A
6.3 A
6.3 A
11 A
11 A
range
6 – 10 A
6 – 10 A
6 – 10 A
6 - 10 A
13 - 18 A
13 - 18 A
Adjustment
8 A
8 A
8 A
8 A
14.8 A
14.8 A
K1
12 A
12 A
12 A
18 A
25 A
25 A
K2
12 A
12 A
12 A
18 A
18 A
18 A
K5
9 A
9 A
9 A
9 A
9 A
9 A
K4
9 A
9 A
9 A
9 A
9 A
9 A
PE
MODELS
GE
AC3 CONTACTOR
FT
FT4
FT5
FT5
FT2
PRESSOST
PRESSOST
PRESSOST
PRESSOST
PRESSOSTA
A
A
A
ATS SETTING
TS SETTING
TS SETTING
TS SETTING
TS SETTING
HP1 : High pressure fixed setting 27,5 bars (400 PSI )
FDP : fixed setting DP on the water circuit 0,05 bar (mod 25/30/35)
MISCELLANEOUS
MISCELLANEOUS
MISCELLANEOUS
MISCELLANEOUS
MISCELLANEOUS
SHM :
Puple shunt to be removed when installing a remote ON/OFF switch between terminals 5 and 6
(40m. maximum).
Note: ON mode = contact closed