Documentation for 

installation and 

operation

HPWH 200 COZY
HPWH 200 COIL COZY
HPWH 270 COZY
HPWH 270 COIL COZY

Heat pump water heater

Summary of Contents for HPWH 200 COIL COZY

Page 1: ...Documentation for installation and operation HPWH 200 COZY HPWH 200 COIL COZY HPWH 270 COZY HPWH 270 COIL COZY Heat pump water heater...

Page 2: ...hildren must not play with the appliance Children must not clean or maintain the appliance without supervision INSTALLATION WARNING Product heavy handle with care 1 Install the appliance in a frost fr...

Page 3: ...s make sure that the power is turned off to prevent any risk of injury or electric shock There must be an omni polar power cut off circuit breaker or fuse fitted upstream of the electrical installatio...

Page 4: ...duct on air exit 5 Not Allowed configurations 6 Hydraulic connection 7 Air connection 8 Electric connection 9 Connection of optional equipment 10 Commissioning Operation 1 Interface 2 Description of p...

Page 5: ...k that the product has been transported and handled in accordance with our recommendations We recommend you should be careful to respect these instructions Our commercial warranty will not apply if th...

Page 6: ...components including the evaporator As it passes through the evaporator the coolant evaporates and conveys calories to the intake air The compressor compresses the coolant causing its temperature to r...

Page 7: ...ump water temperature setting range C 50 to 62 Heat pump user temperature setting range air temperature C 5 to 43 Duct diameter mm 160 Air flow without duct at low speed m3 h 300 Air flow without duct...

Page 8: ...nsate outlet 1221 1221 1562 1562 B Total height 1609 1609 1949 1949 C Cold water inlet 304 462 304 462 D Hot water outlet 961 961 1300 1300 E Total width 620 620 620 620 F Total depth 665 665 665 665...

Page 9: ...an plate support 23 Front column 24 Lower column plug 25 ACI wire 26 Regulation controller PCB 27 Compressor wire 28 Water sensor wire 29 Electrical backup wire 30 Heat pump sensors wire 31 Fan wire 3...

Page 10: ...below the water heater The non respect of installation guidelines can cause poor performances of the system 1 Product installation The device has to fixed according article 20 of EN 60335 1 on the gr...

Page 11: ...where average yearly temperature is 10 C Keep a free space of 500 mm in front of electric compartment and 300 mm around hydraulic connections to allow easy access for maintenance Examples Garage recov...

Page 12: ...water heater and or ducts near to sleeping rooms Examples Washing room Storage room Cupboard in entry area 670mm mini Keep a free space of 500 mm in front of electric compartment and 300 mm around hyd...

Page 13: ...e room generated by the air extraction causes fresh air entry through doors and windows Plan an air entry 160mm from outside to avoid air sucking from heated living area In winter time the renewed air...

Page 14: ...nection to an underground air duct Water heater installed in a room together with a boiler connected to a chimney with natural draft and 1 duct to outside Direct air connection to a cloth drying machi...

Page 15: ...om installation The installation has to include a new safety valve set to 7 bar 0 7 Mpa compliant to EN 1487 and connected directly on the cold water inlet No hydraulic device stop valve pressure redu...

Page 16: ...g through the exchanger forms condensation from humidity in the air The condensed water is evacuated on the rear of the tank using the supplied plastic tube 6 3 Connection of circulation loop Do not c...

Page 17: ...xing screws of the air connection then turn in the required direction Rotate again by 120 position to the opposite sides Rotate by 120 position to the rear A poor duct installation duct compressed len...

Page 18: ...gid conductors with section of 1 5 mm The installation is composed of A 16A omni polar circuit breaker with contacts opening at minimum 3mm A 30mA differential circuit breaker If the power cable is da...

Page 19: ...Once the photovaltaic panels produce enough energy the inverter sends a signal to the water heater which switchs into a special mode PV activating the heat pump If the inverter signal stops the water...

Page 20: ...ction dry contact Electricity supplier Signal 230V 50Hz Power threshold mini 700W Inverter PV panels Signal 230V 50Hz Available power Connect to B1 B2 Junction box Electricity supplier Signal 230V 50H...

Page 21: ...n should be done on the contacts B1 and B2 of the connection board 9 3 Connection to a solar station Electric power supply Solar contact 230V A1 A2 B1 B2 C1 C2 Overview Installation Operation Maintena...

Page 22: ...message appears on the screen At the first switching on the setting instructions are shown on the display Follow thoroughly the instructions on the display to set the parameters Date and time Air duct...

Page 23: ...MODE INSTALLER Press and hold the button MENU and rotate the knob a half turn to the right To exit the installer mode proceed in the same way or wait for 3 minutes Access to parameters Settings rotate...

Page 24: ...ater heater operates only on the electric backup heater Circulation cycle This mode is mandatory when a circulation loop is installed The set temperature changes to 65 C and the operation of the heat...

Page 25: ...The water heater analyses the water consumption of the previous days to adapt the hot water production as required It reacts to unplanned events by launching working cycles during the day to assure en...

Page 26: ...ate Reduce Increase the values Return to previous screen Confirm 2 Description of pictograms Fast heating confirmed Absence registered in operation Present hot water temperature Waiting Warning Electr...

Page 27: ...ing the absence period the water temperature remains above 15 C This function can be interrupted at any moment Stop absence Display the energy savings Allows to display the working level of the heat p...

Page 28: ...user between 50 and 62 C The water heater chooses preferably the heat pump The boiler backup can be activated automatically to provide the correct hot water volume If the backup through the boiler is...

Page 29: ...ecurity group 1 to 2 times per month Operate the safety valve Check that water evacuation is ok General 1 time per month Check external shape of your device no Error code displayed no leakage on the c...

Page 30: ...Check the correct working of the heat pump Components of the heat pump Every 2 years Check the ventilator operation on it s 2 speeds and the hot gas valve Evaporator Every 2 years Clean the evaporato...

Page 31: ...ric backup Resetting automatically at T 10 C Control the situation of the installation room frost free Error 21 Air intake probe defect or out of measuring range HP stopped Heating with electric backu...

Page 32: ...t stop more than 24h or lack of power HP stopped Heating with electric backup Check the cleanness of the evaporator High consumption or circulation loop or leak on hot water circuit Check the connecti...

Page 33: ...counter does not exceed 5 bar 0 5 MPa if it does install a pressure reducer set to 3 bar 0 3 MPa at the start of the water network The electric backup heater does not work Mechanical security thermost...

Page 34: ...fitted new safety unit NF D 36 401 or equivalent modification of calibration etc Missing dielectric union cast iron steel or insulating on hot water connection pipes leading to their corrosion Faulty...

Page 35: ...rge no holding tank for instance or problems with access cannot in any case be blamed on the manufacturer The provisions of this warranty do not exclude the purchaser s enjoyment of the legal warranty...

Page 36: ...or small speed ventilator 17 Controller 18 Regulation PCB 19 Customer wiring board 20 Permanent power supply cable Not supplied 21 Connection cable PV Smart Grid Solar 22 Connection cable boiler 9 Com...