Three-phase photovoltaic grid-connected inverter Display operation panel
54
Item
LCD display
Instruction
Set power
Set power
Power limit mode
Power amplitude
Power factor
Power limit mode: Invalid
Invalid
Automatic
Manual
Power amplitude
100%
Power factor
Grid-connected mode
Common mode
Power factor value: 1.00
Input password
0000
When entering “setup power” interface,
password authorization is required, this
can be acquired from the supplier. This
menu is divided into three sub-menus:
①
Power limit mode: invalid mode (namely
power limit function is invalid); automatic
mode (specific for single-phase
machine); manual mode (set the output
power amplitude manually);
②
Power
amplitude: this function is effective only
when power limit mode is manual, the
percentage ratio is that of the rated
power, the setting range is 10%
–100%;
③
Power factor: Divided into common
mode (default is 1), current lead, and
current lag mode, setting range is 0.9
–
0.99 (3-phase machine currently carries
③
Power factor function only)
Individualize
d setup
Individualized setup
MPPT start voltage
MPPT voltage
120V
Input password
0000
This function is effective on single-phase
machine. When entering “individualized
setup” interface, password authorization
is required, this can be acquired from the
supplier. The sub-menu of this menu is
“MPPT start voltage” menu, which can set
the start voltage of MPPT mode, the
setup is 120V
–160V