CHV100 Series Close Loop Vector Control Inverter
.86.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.15
Latest fault type
0~30
0~30
These parameters record three recent fault types. For details, please refer to description
of chapter 7.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.16
Output
frequency
at current
fault
Output frequency at current fault.
P7.17
Output
current at
current
fault
Output current at current fault.
P7.18
DC bus
voltage at
current
fault
DC bus voltage at current fault.
P7.19
Input
terminal
status at
current
fault
This value records ON-OFF input terminal
status at current fault. The meaning of each
bit is as below:
9 8 7
6
5
4 3 2 1 0
S8 S7 S6 HDI2 HDI1 S5 S4 S3 S2 S1
1 indicates corresponding input terminal is
ON, while 0 indicates OFF.
Notice: This
value is displayed as decimal.
P7.20
Output
terminal
status at
current
fault
This value records output terminal status at
current fault. The meaning of each bit is as
below:
BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
RO3 RO2 RO1 HDO Y2 Y1
1 indicates corresponding output terminal is
ON, while 0 indicates OFF.
Notice: This
value is displayed as decimal.