INVOLAR Corporation, Ltd.
Manual version 1.12
INVOLAR Corporation Ltd. Mar. 2016
13
ignored, physical injury or death may follow, or damage may occur to the unit.
Read these instructions before you work on the unit. If you are unable to understand
the Dangers, Warnings, Cautions or Instructions, contact the manufacturer or an
authorized service dealer before installing, operating and servicing the unit.
The Grid Connected Inverter meets the requirements stipulated in Low Voltage
Directive (LVD) 2006/95/EC and Electromagnetic Compatibility (EMC) Directive
2004/108/EC. The unit is tested based on:
EN 62109-1:
EN 61000-6-1;
EN61000-6-2;
EN61000-6-3;
UL1741/IEEE1547
When installing the PV system, startup of the unit (i.e. start of designated operation) is
prohibited until it is determined that the full system meets the requirements stipulated
in the EC Directive (2006/95/EC, 2004/108/EC etc).
The grid connected Inverterleaves the factory completely connecting device and
ready for connection to the mains and PV supply. The unit shall be installed in
accordance with national wiring regulations. Compliance with safety regulations
depends upon installing and configuring system correctly, including using the
specified wirings. The system must be installed only by competent assemblers who
are familiar with requirements for safety and EMC. The assembler is responsible for
ensuring that the end system complies with all the relevant laws in the country where
it is to be used.
The individual subassembly of the system shall be interconnected by means of the
wiring methods outlined in national/international regulations but not limited to the
BS7671 Requirements/ VDE regulation 0107.
[Use Condition]
1. Overvoltage category:overvoltage category III for MAINS connection,
overvoltage category II for PV supply according to IEC/EN 60664-1.
2. Pollution degree: Pollution degree III, not intended for heavy pollution of the air by
dust, smoke, corrosive or radioactive particles, vapors or salt.
3. Class of protection: I.
4. Protection against ingress of water: IP65
WARNINGS
The Degree of protection rating IP65 to IEC 60529 is applicable to
the device when the supplied installation connectors are inserted
correctly, and suitable external cord was fitted. If the unit is not
connected in this way, hazardous live parts may be exposed and
the IP Rating of the unit will be invalid
5. The equipment is rated to operate at an altitude less than 2000 m.